PureAire Monitoring Systems, Inc.
33
After entering the relay state by pushing the joystick left, the display will default back
to the Set Latching Audio Alarm menu. The display will scroll the following:
5.5.5 Resetting a Latching Alarm
To reset a latching alarm relay, you must enter the password correctly and then push the
joystick IN to enter the reset command. The Universal Gas Detector also has an
internal
2-pin terminal block for connecting a remote reset switch. (See Alarm Relay board,
section 1.2.7)
5.5.6 Set Alarm Delay
Push the joystick down to access the next main menu,
Alarm Delay.
The display will
scroll the following:
This is the amount of time an alarm level concentration of gas must be present
before the instrument’s gas concentration alarm(s) will be activated. This menu will
permit setting a user selected time delay for activating alarm relays 1 and 2. You can
select from 0 seconds up to 255 seconds after an alarm level has been exceeded before
the alarm relays will activate.
To change this value, push the joystick right to display the Alarm Delay screen. The
display will indicate a value between 0 and 255 seconds. Pushing the joystick up
increases the value and pushing the joystick down decreases the value.
After entering the delay time pushing the joystick left, the display will default back to
the Alarm Delay menu. The display will scroll the following:
NOTE: Setting the alarm delay will operate simultaneously for both alarms 1 and 2.
There is no delay for the fault relay. Any system fault will immediately
activate the Fault Relay.
..Set Latching Audio Alarm…
0.0 ppm
…Alarm Delay…
0.0 ppm
005
0.0 ppm
…Alarm Delay…
0.0 ppm