P8400W Air-dryer User’s Guide
Page 106 of 110
P017585 – Rev. A
14.2 Set Point Limits and Defaults
14.2.1
System Adjustments
14.2.2
Alarm Set Points
Description
Minimum
Value
Maximum
Value
Default
Value
Unit of
Measurement
Shutdown
High Flow Alarm
100
40,000
4,500
SCFD
High Outlet Pressure
Alarm
0.2
20.0
12.0
PSI
Low Outlet Pressure
Alarm
.1
19.9
6.5
PSI
High Humidity Alarm
3.0
15.0
10.0
%
YES
Excessive Compressor
Run Time Alarm
1:00
59:59
3:00
Minutes :
Seconds
14.2.3
System Operations
14.2.4
SNMP Parameters
Device Configuration Information
Device ID
Alphanumeric (Defined by Customer)
Device Model
Alphanumeric (Factory Preset)
Device Firmware Version
Numeric (Factory Preset)
Current Date/Time
Numeric (mm/dd/yy hh:mm)
IP Address
Numeric (xxx.xxx.xxx.xxx)
Subnet Mask
Numeric (xxx.xxx.xxx.xxx)
Gateway Address
Numeric (xxx.xxx.xxx.xxx)
SNMP Trap Server Address
Numeric (xxx.xxx.xxx.xxx)
SNMP Read Community String
Alphanumeric (6-14 digits, Default =
Description
Minimum
Value
Maximum
Value
Default
Value
Unit of
Measurement
System Pressures
48.0
52.0
50.0
PSI
Static Pressure
17.0
17.0
17.0
PSI
Outlet Pressure
1.0
15.0
10.0
PSI
Description
ON Value
OFF Value
Default
Value
Unit of
Measurement
Compressor
20.0
50.0
PSI
High Cabinet
Temperature Alarm
140.0
Deg F
High Compressor
Temperature Alarm
140.0
Deg F
Compressor Total Run
Time Reset
8,000
Hours