Altec AIR
P8400W Air-dryer User’s Guide
Page 29 of 110
P017585 – Rev. A
SYSTEM*
- Running Status of System*:
ONLINE
– System* is Online in the dryer cycle mode.
STANDBY
– System* is not Online in the dryer cycle mode.
SHUTDOWN
– System* has been shutdown as a result of either a
Humidity, High Compressor Temperature, or High Cabinet
Temperature alarm.
HUMIDITY
– Humidity level of System*.
DUTY CYCLE
– The percentage of time that the compressor was on
during the last compressor pump-up cycle
8.4.4.4
System Runtime Screens
LAST
– Last compressor runtime in minutes
TOTAL
– Total compressor runtime in minutes
8.4.4.5
System Cycle Mode Screen
Displays the current System Cycle Mode setting:
24 HOUR CYCLE
– Cycles between System 1 & System 2 every
24 hours (when the
TIME
reaches 24:00). Puts one system Online
and the other in Standby.
BOTH
– Runs both System 1 and System 2 simultaneously.
SYSTEM 1 ONLY
– Runs only System 1 and leaves System 2 in
Standby.
Summary of Contents for Altec AIR P8400W
Page 1: ...P017585 Rev A P8400W Air dryer User s Guide...