9.3 Measuring Compressor Voltage
9.3.1
Power the air dryer
OFF
9.3.2
Open Front Panel (section 8.6 ).
9.3.3
Depressurize the air dryer (section 8.7 ).
9.3.4
Locate wire #5 at the solid
state relay and wire #6 on
Control Board.
9.3.5
Lift plastic cover on
Control Board over wire #6.
9.3.6
Power the air dryer ON
9.3.7
Use a Voltmeter to measure
the voltage:
9.3.7.1
Place the probes over
terminals for wire #5
and wire #6.
The voltage should measure:
110 - 125 VAC
for the
P1500W, P1500WLP &
P1500WHP models
208 - 230 VAC
for the P1502W, P1502WLP & P1502WHP models
9.3.8
Close plastic cover on Control Board over wire #6.
9.3.9
Close Front Panel.
WARNING!
Extreme care should be exercised to avoid contact with live
electrical circuits.
It is highly recommended that you remove all
jewelry before performing any procedures.