ALTEC AIR, LLC
P1500W Series Air Dryers User’s Guide
Page 66 of 100
P011787 – Rev. S
9.12 Testing High Compressor Last Run Time Alarm
NOTE:
For this test, allow the Display Screen to cycle through the information
screens.
9.12.1
Open Front Panel (section 8.6 ).
9.12.2
Start timing when the Compressor turns on.
9.12.3
Pull the ring handle on the
Safety Relief Valve (when
necessary) to keep the Tank
Pressure (
TANK
) from
reaching
90 PSI.
This prevents the Compressor
from shutting down.
When the Compressor runs
for 3:00 minutes (unless
adjusted to a different Set
Point by the user), a High
Compressor Last Run Time
(
LAST RUN
) alarm should
appear on the System Screen.
9.12.4
Press the
RESET Button
.
9.12.5
Close Front Panel.
If you are unable to create a High Compressor Last Run Time (LAST RUN)
alarm as described, see section 0for troubleshooting information.