PUREGAS, LLC
P4200W2 Series Air Dryer User’s Guide
Page 82 of 113
P012308 - Rev. E
9.15.7
Turn Outlet Pressure
Regulator knob counter-
clockwise until Outlet
Pressure (
OUTLET
) reading
lowers to the reading
recorded in step 9.15.1
9.15.8
Push knob in to lock.
9.15.9
Reinstall the Front Panel (section 8.10 ).
If you are unable to create a High Outlet Pressure Alarm as described, see
section 13.6 for troubleshooting information.
9.16 Testing Low Outlet Pressure Alarm
9.16.1
Make a note of the current
Outlet Pressure (
OUTLET
)
reading.
9.16.2
Remove the Front Panel
(section 8.10 ).
With Compressor running:
9.16.3
Pull the Outlet Pressure
Regulator knob out.
9.16.4
Turn knob counter-
clockwise until Outlet
Pressure (
OUTLET
) reading
drops below the alarm
threshold. (section 8.8.7 )
Summary of Contents for P4200W2