PUREGAS, LLC
P550W2 Series Air Dryers User’s Guide
Page 96 of 99
P012226 – Rev. F
14.3 SNMP Parameters
Device Configuration Information
Device ID
Alphanumeric (Defined by Customer)
Device Model
Alphanumeric (Factory Preset)
Device Firmware Version
Numeric (Factory Preset)
Current Date/Time
Numeric (mm/dd/yy hh:mm)
IP Address
Numeric (xxx.xxx.xxx.xxx)
Subnet Mask
Numeric (xxx.xxx.xxx.xxx)
Gateway Address
Numeric (xxx.xxx.xxx.xxx)
SNMP Trap Server Address
Numeric (xxx.xxx.xxx.xxx)
SNMP Read Community String
(also sets SNMP Trap Community String)
Alphanumeric (6-14 digits, Default =
“public”)
SNMP Write Community
Alphanumeric (6-14 digits, Default =
“123456”
Status Readings (Read-Only)
Outlet Pressure Reading
Numeric (KPa)
Tank Pressure Reading
Numeric (KPa)
Humidity Reading
Numeric (%)
Flow Reading
Numeric (SCMD)
Cabinet Temperature Reading
Numeric (DEG C)
Compressor Total Run Time Reading
Numeric (Hours)
Duty Cycle Reading
Numeric (%)
System Status
ON / SHUTDOWN
Compressor Status
ON / OFF
Fan Status
ON / OFF
Heater Status (Outdoor Unit Only)
ON / OFF
Alarm Readings (Read-Only)
High Flow Alarm
OK / Alarm
High Outlet Pressure Alarm
OK / Alarm
Low Outlet Pressure Alarm
OK / Alarm
High Humidity Alarm
OK / Alarm
High Cabinet Temperature Alarm
OK / Alarm
High Duty Cycle Alarm
OK / Alarm
Maintenance Required Alarm
OK / Alarm
Total Alarm
OK / Alarm
Configuration Settings (Read-Write)
High Flow Alarm Threshold
Numeric (SCMD)
High Outlet Pressure Alarm Threshold
Numeric (KPa)
Low Outlet Pressure Alarm Threshold
Numeric (KPa)
High Humidity Alarm Threshold
Numeric (%)
High Duty Cycle Alarm Threshold
Numeric (%)
Reset Compressor Total Run Time Reading
Numeric (Hours)
Start Up Delay Time
Numeric (Seconds)
Alarm Reset
RESET
Alarm Delay
ON / OFF
Alarm Traps Sent to SNMP Server
High Flow
High Outlet Pressure
Low Outlet Pressure
High Humidity
High Cabinet Temperature
High Duty Cycle
Maintenance Required