PUREGAS, LLC
P6500W Air Dryer User’s Guide
Page 12 of 88
P010452 – Rev. Q
6.2 Before You Begin
6.2.1 Carefully inspect the unit, including the shipping box as well as the air
dryer, for ANY DAMAGE CAUSED BY SHIPPING. If any shipping
damage is detected, it is important to file a claim with the shipping
company prior to continuing the installation procedures.
6.2.2
Read the entire
Installing Your Dryer
section to familiarize yourself with
the components and procedures before performing the air dryer installation.
6.2.3
Verify the installation location of the air dryer:
6.2.3.1
Well ventilated and free from abrasive dust or chemicals.
6.2.3.2
Ambient temperature is between 40° and 85° F (optimal).
NOTE:
Higher temperatures will decrease component lifespan.
6.2.3.3
Meets the following power requirements:
190 -230 VAC, 1 P
hase, 50 / 60 Hz
Minimum 20 amp service circuit breaker or slow blow fuse
Outlet compatible with a HBL9965C plug
If hard-wiring directly, minimum of 12 AWG wire must be used
6.2.4
Notify the alarm center of the installation and potential for alarms during
the process (as necessary).
IMPORTANT!
Performing procedures not described in this User’s Guide or
installing components not supplied by PUREGAS is NOT
RECOMMENDED AND MAY VOID THE WARRANTY.
IMPORTANT!
Installation of PUREGAS air dryers are intended for network
telecommunication facilities (non-customer premises) only.