PUREGAS, LLC
P6500W Air Dryer User’s Guide
Page 34 of 88
P010452 – Rev. Q
8.6.4 High Humidity Alarm Set Point
(default setting is 10.0%) –
8.6.4.1
Press the Right (
) Arrow
Button to access the Change
Value Screen.
8.6.4.2
Press the Right (
) &
Left (
) Arrow Buttons to
move the underscore beneath
the digit to change.
8.6.4.3
Press the Up (
) & Down (
) Arrow Buttons to change the value of
the selected digit.
8.6.4.4
Press the Right (
) Arrow Button until the underscore disappears.
This will lock in the new setting value.
8.6.5 Excessive Compressor Run Time Alarm Set Point
(default setting is 3:00
minutes) –
8.6.5.1
Press the Right (
) Arrow
Button to access the Change
Value Screen.
8.6.5.2
Press the Right (
) &
Left (
) Arrow Buttons to
move the underscore beneath
the digit to change.
8.6.5.3
Press the Up (
) & Down (
) Arrow Buttons to change the value of
the selected digit.
8.6.5.4
Press the Right (
) Arrow Button until the underscore disappears.
This will lock in the new setting value.