PUREGAS, LLC
P6500W Air Dryer User’s Guide
Page 85 of 88
P010452 – Rev. Q
14.2 Set Point Limits and Defaults
14.2.1
System Adjustments
14.2.2
Alarm Set Points
Description
Minimum
Value
Maximum
Value
Default
Value
Unit of
Measurement
Shutdown
High Flow Alarm
100
40,000
4,500
SCFD
High Outlet Pressure
Alarm
0.2 20.0 12.0 PSI
Low Outlet Pressure
Alarm
.1 19.9 6.5 PSI
High Humidity Alarm
3.0
15.0
10.0
%
YES
Excessive Compressor
Run Time Alarm
60.00 59:59 180.00 Seconds
14.2.3
System Operations
Description
ON Value
OFF Value
Default
Value
Unit of
Measurement
Compressor 20.0
50.0
PSI
High Cabinet
Temperature Alarm
14.0
Deg
F
High Compressor
Temperature Alarm
140.0
Deg
F
Compressor Total Run
Time Reset
8,000
Hours
Description
Minimum
Value
Maximum
Value
Default
Value
Unit of
Measurement
System Pressures
48.0 52.0 50.0 PSI
Static Pressure
17.0 17.0 17.0 PSI
Outlet Pressure
1.0
15.0
10.0
PSI