background image

14 

Reverse Osmosis Water Treatment System

Copyright © Puretec Pty Ltd 2020

To Care for the RO System

The components of the RO system are designed to function with minimal maintenance. 

However, the membrane elements and filters will need to be replaced on a regular schedule.

For optimal performance the system should be flushed for 2 minutes if periods of inactivity 
extend past six hours.

Replacement of Prefilter and Post Filter

The carbon/sediment prefilter reduces sediment and certain chemicals, such as chlorine, from 
the water. Depending on water use and the amount of impurities, this filter should be replaced 
every six to twelve months for point-of-use applications.

Whenever the prefilter is replaced, the post filter should also be replaced.

Installations using more than 20 gallons product water per day should install external filters (not 
supplied) to reduce chlorine and sediment larger than 10 microns.

Replacement of RO Membrane Elements

The functional life of the RO membrane elements will vary based on feed water quality. Product 
water should be tested periodically to verify the membrane elements are performing properly. 

For most point-of-use applications, the RO membrane elements should be replaced every two 

to four years.

Note

: Softened water is recommended for optimal system 

performance and RO membrane element life.

Replacement of the Prefilter, Post filter, and RO Membrane Elements

1.  Turn off the water supply to the RO System.

2.  Reduce system water pressure by opening the faucet.

Caution

: Even with the water supply turned off the membrane and 

prefilter sumps will contain a considerable amount of water. By 

positioning the RO assembly in a sink or tub, most of the water will 
be contained.

3.  Disconnect locking bar and place the fittings (with tubing 

still connected) into a tub or bucket.

4.  Move system into a contained area, such as a sink or tub.

5.  Remove the support leg from the three sumps and unscrew the top sump as shown 

to access the prefilter element. The support leg functions as a wrench to loosen the 
sump, Figure 12.

RO Installation Guide

will need to be replaced on a regular schedule.
For optimal performance the system should be flushed for 2 minutes if 

periods of inactivity extend past six hours.

REPLACEMENT OF PREFILTER AND POSTFILTER 

The carbon/sediment prefilter reduces sediment and certain 

chemicals, such as chlorine, from the water. Depending on water use 

and the amount of impurities, this filter should be replaced every six  

to twelve months for point-of-use applications.
Whenever the prefilter is replaced, the postfilter should also be 

Installations using more than 20 gallons product water per day should 

install external filters (not supplied) to reduce chlorine and sediment 

larger than 10 microns.

REPLACEMENT OF RO MEMBRANE ELEMENTS

The functional life of the RO membrane elements will vary based 

on feed water quality. Product water should be tested periodically 

to verify the membrane elements are performing properly. For most 

point-of-use applications, the RO membrane elements should be 

replaced every two to four years. 

NOTE: Softened water is recommended for optimal system 

performance and RO membrane element life.

REPLACEMENT OF THE PREFILTER, 
POSTFILTER, AND RO MEMBRANE ELEMENTS

1.  Turn off the water supply to the RO System.  
2.  Reduce system water pressure by opening the faucet.

  Even with the water supply turned off the membrane and 

prefilter sumps will contain a considerable amount of 

water. By positioning the RO assembly in a sink or tub, 

most of the water will be contained.

3.  Disconnect locking bar and place the fittings (with tubing still 

connected) into a tub or bucket.

4.  Move system into a contained area, such as a sink or tub.
5.  Remove the support leg from the three sumps and unscrew the 

top sump as shown to access the prefilter element. The support 

leg functions as a wrench to loosen the sump, Figure 13.

NOTE: There is no need to disconnect tubing from fittings on the 

manifold. Remove locking bar and pull fittings out. Lubricate 

O-rings with silicone prior to re-assembly.

NOTE: If changing only the prefilter and postfilter, the other sumps do 

not need to be removed.   

If changing the membrane elements,  the prefilter and 

postfilter should also be changed. 

6.  Remove exhausted prefilter and discard.

  The person handling the filters and membrane elements 

must have clean hands to keep the system sanitized.  The 

use of sterile/latex gloves is recommended.

7.  If changing membrane elements:

a.  Remove membrane sumps. Remove and discard used 

elements.

b.  Remove new elements from packaging.

Figure 13   

Fig. 12

Summary of Contents for ROS2700

Page 1: ...User Guide Reverse Osmosis Water Treatment System ROS2700 For correct operation installation it is essential to observe these instructions SEPT2020...

Page 2: ...laboratory every six months The laboratory should be certified for testing the specific contaminants of concern For a listing of certified laboratories contact local regulatory agencies Consult your l...

Page 3: ...limits A water quality analysis can be performed to determine if incoming water requires any treatment Contact your dealer installer The filters and membrane elements in the RO system need to be repl...

Page 4: ...AR INSTALL KIT LOCKING BAR DISCONNECT 3 8 INCH COLLET LOCK CLIP 1 2 INCH COLLET LOCK CLIP SOME CONFIGURATIONS MAY NOT INCLUDE ALL COMPONENTS LISTED BELOW TUBING INSTALL KIT 3 8 BLACK TUBING 4 ft 3 8 B...

Page 5: ...RO membrane element Drain Point A suitable drain point is needed for reject water from the RO system A floor drain laundry tub standpipe sump etc are all acceptable If discharging into the utility sin...

Page 6: ...r Gap 1 5 Air Gap Required Inlet 1 2 Natural Drain 3 8 Black Feed Water Valve Cold Water Line Only Carbon Postfilter Product 3 8 Blue RO Assembly Keep to Minimum THE BASIC REVERSE OSMOSIS SYSTEM cont...

Page 7: ...Line Only Feed Pressure Gauge RO Assembly External Prefilter Product Storage Tank To Point of Use Vented to Atmosphere Liquid level float sensor to control feed solenoid valve Feed Solenoid Valve Figu...

Page 8: ...t Be sure it will fit flat against the sink or counter and that there is space underneath for tubing 2 If drilling is needed make a 1 1 2 inch diameter hole Warning To avoid damaging a sink consult a...

Page 9: ...nst the clip to hold the faucet in position Installation Guide ater supply and open a low faucet to d style The installer will determine nstall a valve on the cold water tubing If threaded fittings ar...

Page 10: ...s intended for use only durin installation and troubleshooting of the RO system The pressure gauge should be removed during normal system operation because some regulatory agencies did not evaluate th...

Page 11: ...e Ensure that the support leg is installed on the sumps Installation Guide NOTE Make sure the tubing is pushed past the O rings for a secure fit Also when replacing any tubing cut tubing back 1 4 inch...

Page 12: ...d Connector Symbol Connection Tubing Colour Feed Inlet Natural Concentrate Black Product Blue Warning Be sure to lubricate the manifold ports with silicone lubricant prior to inserting the fittings in...

Page 13: ...side 4 Purge the system Open the faucet and run the water through the RO system for two to eight hours Note A minimum of 2 hour flush is required to remove the food grade preservative After 8 hours pe...

Page 14: ...ystem into a contained area such as a sink or tub 5 Remove the support leg from the three sumps and unscrew the top sump as shown to access the prefilter element The support leg functions as a wrench...

Page 15: ...ain a food grade preservative The use of sterile latex gloves is highly recommended c Lubricate element O rings brine seals and sump O rings with silicone lubricant Refer to Connection Lubrication on...

Page 16: ...w direction arrow aligns with water path Reinsert tubing and collect locks 11 Re connect the fittings to the manifold and lock in position with locking bar 12 Re position the assembly and turn the wat...

Page 17: ...Inlet Turbidity 0 1 NTU Dimensions Performance Specifications Minimum and Maximum Operating Conditions Condition Minimum Maximum Inlet Pressure 40 psi 2 76 bar 80 psi 5 52 bar Inlet Temperature 40 F 4...

Page 18: ...lugged post filter If flow into the post filter is acceptable replace post filter Leak or kink in product line Find and repair leak or kink Concentrate water runs to drain after faucet shut off Plugge...

Page 19: ...19 Copyright Puretec Pty Ltd 2020 Reverse Osmosis User Guide Installation Information 14...

Page 20: ...ed or replaced if the goods fail to be of acceptable quality and the failure does not amount to a major failure Warranty New Zealand This warranty is given by Puretec Ltd Reg No 4464398 PO Box 875 Cam...

Reviews: