PV500-57 06/12
11
FIGURE 4
FIGURE 5
3
Ø
AMPS PER ELEMENT
1
Ø
AMPS PER ELEMENT
KW-
VOLTAGE
AMPS PER
LEG
AMPS
TOTAL
AMPS PER
LEG
AMPS
TOTAL
*14 kW-600V
13 1/2
13 1/2
—
—
*7 kW-600V
7
7
—
—
18 kW-600V
18
18
—
—
9 kW-600V
9
9
—
—
4.5 kW-600V
4 1/2
4 1/2
—
—
18 kW-480V
22
22
—
—
9 kW-480V
11
11
—
—
4.5 kW-480V
5 1/2
5 1/2
—
—
18 kW-380V
28
28
—
—
9 kW-380V
14
14
—
—
4.5 kW-380V
7
7
—
—
18
kW-240V
44 44 25 75
9
kW-240V
22 22 13 38
4.5 kW-240V
11
11
6
18
18
kW-208V
50 50 29 87
9
kW-208V
25 25 15 44
4.5 kW-208V
12 1/2
12 1/2
7
22
TABLE 2
NOTE:
Elements are
usually
wired to contactors in groups, in order to maintain an amperage draw of close to, but not more
than, 50 amps per contactor.
*Applications for 600V may be a re-rated 480V element. Therefore, the 40W/in.
2
may be rated for 14 kW instead of
9 kW.