5. Check The Vent Pressure
With the combustion properly adjusted, now use the test hole in the flue vent to measure the vent pressure.
With the burner firing, confirm the vent pressure does not exceed .5” W.C. Pressure in excess of .5” W.C.
indicates a venting sizing issue that must be addressed by the installer before operating the water heater.
WARNING: When adjustments are complete and before putting the water heater into service, return the
MAN OVR function back to “AUTO”. Failure to return the MAN OVR function to “AUTO” can cause high
water temperatures that can result in property damage, scalding, other serious injury or death
.
Gas Train Illustration for Models 50 through 80
(Optional components may not be shown)
16. POTENTIOMETER (Adjusting the Setpoint)
The PIM Ignition Control will continue to operate the Conquest water heater at a 120 degree internal factory setpoint
should the touch screen control fail, or communication between the two devices is interrupted. This internal setpoint
can be adjusted using the potentiometer to maintain a different operating temperature under these circumstances if
desired.
To Adjust The PIM Potentiometer Setpoint:
1. From the View Menu, press and hold the
HOME
button for 3 seconds to display the SETUP Menu.
2. Using
the
NEXT ITEM
or
ITEM BACK
buttons navigate to the
TOOLBOX
menu, then touch the
ENTER
button
to display the
ACCESS
menu.
3. Now use the
UP
or
DOWN
arrow buttons to select the
INSTALLER
setting.
4. Touch
the
HOME
button to return to the
TOOLBOX
menu, then use the
NEXT ITEM
or
ITEM BACK
buttons
to
navigate to the
SOURCE
menu.
5. Touch
ENTER
to
enter the source menu and use the
NEXT ITEM
or
ITEM BACK
buttons to navigate to the
OPERATOR
screen to display the potentiometer setpoint.
6. Open the hinged upper panel of the control enclosure and locate the potentiometer on the PIM Ignition Module.
7. Using a small blade screwdriver, manually adjust the PIM Potentiometer to a desired stand-alone setpoint
temperature as you view the adjusted temperature setting in the
OPERATOR
screen.
8. Exit the menu by pressing the
HOME
button.