Grounding conductor must adopt copper conductor in order to reduce high
frequency impedance, and the grounding wire must be as thick and short as
possible.
Users should make sure the 2 ends of grounding wire well electric conducted and
be antirust.
It is prohibited to use any other device as part of grounding electric circuit
The area of the conduction between grounding wire and device’s frame should
be no less than 25mm
2
.
2.2.4 Frame Grounding
All the machine frames should be connected with protective copper strip. The
grounding wire should be as short as possible and avoid circling. The area of the
conduction between grounding wire and grounding strip should be no less than
25mm
2
.
2.2.5 Device Grounding
Connecting th
e device’s grounding rod to frame’s grounding pole with copper wire.
2.3 Wire’s Connection
The grounding wire conductive screw is located at the right end of rear panel, and the
power switch, fuse, power supply socket is just beside ,whose order goes like this,
power switch is on the left ,power supply socket is on the right and the fuse is just
between them.
Connecting Power Cord
User can insert one end into power supply socket, while insert the other end to
AC power.
Connecting Grounding Wire
When the device solely connects to protective ground, it should adopt
independent way, say, share the same ground with other devices. When the
device adopts united way, the grounding resistance should be smaller than 1Ω.
Caution:
Before connecting power cord to MTRX IRD, user should set the power switch