background image

Product is patented in the U.S., Canada, and Mexico. 

 

PVI INDUSTRIES, LLC 

FORT WORTH, TEXAS 76111 

PV 5369  07/04

 

(800) 784-8326  

  www.pvi.com 

ATMOSPHERIC GAS  •  PACKAGED WATER HEATER 

NICKELSHIELD

®

 - NICKEL-PLATED STORAGE TANK 

TANK SERIES 125 GALLONS 

 

Recovery gph 

c

 Dimensions 

(inches) 

Model Number 

40° - 120°F 

40° - 140°F

Input 

Btu/h 

* Min. Inlet Flow 

Gas Pressure 

"W.C. 

B C E 

Shipping 

Weight 

lbs 

14 N 125A-G 

168 

134 

140,000 

4.5 

3/4 

86 

980 

20 N 125A-G 

239 

191 

199,000 

4.5 

3/4 

86 

1030 

27 N 125A-G 

324 

259 

270,000 

4.5 

3/4 

86 

1090 

40 N 125A-G 

479 

383 

399,000 

4.5 

3/4 

87 

1170 

54 N 125A-G 

648 

518 

540,000 

6.5 

10 

87 

1330 

72 N 125A-G 

864 

691 

720,000 

6.5 

12 

87 

1430 

80 N 125A-G 

960 

768 

800,000 

7.0 

12 

1 1/4 

87 

1490 

c

 Recoveries based on 80% thermal efficiency. ASHRAE 90.1 compliant for efficiency and standby loss. 

*  The information presented is for natural gas 0.6 S.G. – For operation with propane (LP gas), consult the factory. 
*  For operation outside this range, consult the factory. 
  Dimensions are in inches unless otherwise notes. 
    For standard and optional equipment, see form #PV 6070. 
 
 
 
 
 
 

 

 
 
 
 
 

STANDARD GAS PRESSURE REQUIREMENTS: 

SEE TABLE FOR MINIMUM PRESSURE BY MODEL NUMBER. 

MAXIMUM STATIC INLET GAS PRESSURE: 14 W.C. 

FOR GAS PRESSURES OUTSIDE OF THIS RANGE,  

CONTACT YOUR PVI REPRESENTATIVE. 

 

ELECTRICAL REQUIREMENTS: 

CONTROL VOLTAGE: 

115V, 1Ø, 60 HZ., 2 AMPS

 

 

VENTING REQUIREMENTS: 

TYPE B VENTING. 

 

ENTIRE VENT SYSTEM SHOULD NEVER BE SIZED BASED 

UPON THE VENT CONNECTION DIAMETER EXCLUSIVELY. 

CHECK NATIONAL FUEL GAS CODE UNDER "ATMOSPHERIC." 

PVI RESERVES THE RIGHT TO CHANGE THE DESIGN AND 

SPECIFICATION WITHOUT NOTICE. 

 