POWER VTX
®
WATER HEATER
22
PV500-68 06/16
When combining the exhausts of multiple POWER VTX
®
water heaters do not use individual remote ducts to provide
outdoor combustion air.
4. When exhaust vents are combined, it is necessary to either:
a. Draw all combustion air for each heater from the mechanical room in which they are installed, or
b. Use a common air supply system that is designed and installed by a qualified professional firm and that
meets all the requirements contained in Subsection
Combining Remote Air Ducting
, which is located in
the
COMBUSTION AND VENTILATION AIR
Section
of this manual.
WARNING: Do not connect multiple water heaters vents into a single unpowered or fixed speed powered
vent. This could cause unsafe operation and the potential for poisonous carbon monoxide to enter occupied
areas. Such improper installation can cause property damage, exposure to hazardous materials, personal
injury or death.
Conventional Venting
Through the Wall Venting
Combining Vents with a Draft Inducer