POWER VTX
®
WATER HEATER
27
PV500-68 06/16
10.4 View Menu (Home Screen - Default Display)
The
View Menu
is the default display (home screen) of the EOS control system. The View Menu displays general
information about the water heater’s operation and status. The default display includes a Burner Firing Rate % Icon
for modulating units (disregard this icon for fixed rate burners), a Pump Icon that is visible whenever the integral
tank circulator is energized and Failure Messages if the unit is in an alarm or error condition.
Use the
Next Item
and
Item Back
buttons to scroll and view the View Menu Item Fields and their associated
values.
The Item Field descriptions are listed below:
Item Field
Description
SETPOINT
Display screen displays the current operating set point but does not allow the user to make
changes in this menu.
VENT
Displays the current flue gas temperature as measured by the flue gas sensor located in the
flue outlet.
TANK TOP
Displays the current temperature at the top of the water heater tank as measured by the
operating control sensor located near the hot outlet.
TANK BOT
Displays the current temperature near the bottom of the water heater tank as measured by
the control sensor responsible for regulating the operation of the integral tank circulator.
TANK
∆
T
Displays the current temperature difference between the TANK TOP and the TANK BOT
sensors.
FLAME CUR
Displays the burner flame current in approximate µA dc. Since this is an approximation it is
recommended that a flame current measurement be taken at the PIM control board using a
micro-amp meter.
TIME
Displays the real time as programed in the TIME menu.
Pump Icon displays whenever the
integral tank circulator is energized
Indication of burner firing rate as
percentage of turndown range.
Home
Button
Home Button.
Return to the ‘Home’
Screen from any menu.
Press and hold for 3
seconds to access the
programming menus.
Menu Icon
The CTRL TEMP is the
operating temperature
sensed at the top of the
tank