12.1 EOS Register List
Parameter
Read/
Write
Type Format
Units
Range
Register
Address
Heater Ignition
Read
Input
U16
Enum
0=IDLE, 1=PREPurge,
2=IGNition, 3=BURNer
on, 4=postPURG,
5=FAIL
101
Upper Tank Temperature
Read
Input
S16
°F
-22 to 266
102
Lower Tank Temperature
Read
Input
S16
°F
-22 to 266
105
Vent Temperature
Read
Input
S16
°F
16 to 300
108
High Limit Temperature
Read
Input
S16
°F
-22 to 266
111
Modulation Rate
Read
Input
U16
%
0 to 100
112
Flame Current
Read
Input
U16
0.1V
0 – 10.0
113
Burner Runtime
Read
Input
U16
Hours
0 – 65535
114
Burner Cycles
Read
Input
U16
Num
0 – 65535
115
Heater Circulator Status
Read
Input U16
Enum
0=Off,
1=On
116
Heater Setpoint Occupied
Read/
Write
Holding
S16
°F
70 to 190
200
Heater Setpoint Unoccupied
Read/
Write
Holding
S16
°F
70 to 190
201
Call For Heat
Read
Input
U16
Enum
0=Call present, 1=Call
not present
15
Heater Enable/Disable
Read/
Write
Holding U16 Enum
0=Off,
1=On
100
Error Code History
Read
Input
U16
See Error Codes 12.2
200-215