PV 6112b  6/03 

SPECIFICATION FOR DOMESTIC WATER HEATERS 

Power Combustion, Oil-Fired Water Heaters with Nickel-Plated Storage Tanks 

 
 
 
 

 

Furnish and install 

TURBOPOWER

® oil water heater(s) as manufactured by PVI INDUSTRIES, INC  

of Fort Worth, Texas.  Supply quantities and model numbers as indicated on the plumbing schedule. 
 

Efficiency 

 
 
 

The water heater will operate at a minimum of 83% thermal efficiency.   The water heater will comply with paragraph 

7.2.4.4, the thermal efficiency, the standby loss, and all other requirements of ASHRAE 90.1-1999. 
 
 

Pressure Vessel and Heating Surfaces 

 
 

The water heater will be constructed and stamped in accordance with Section IV, Part HLW of the ASME code.   

 
 

The storage section of the water heater will be National Board Registered for a working pressure of  ____ 125 psi 

(standard) or ____ 150 psi and will be pressure tested at 1-1/2 times working pressure.  The heating section of the water 
heater will be National Board Registered for a working pressure of 150 psi and will be pressure tested at 1-1/2 times 
working pressure.   
 
 

The heat exchanger will be a firetube design with the combustion chamber and all heating surfaces completely 

water-backed.  The fireside of the combustion chamber will be of boiler-grade steel.  The waterside of the combustion 
chamber will be non-ferrous. The fire tubes will be solid copper.  The heating surfaces will be removable by unbolting 
from the pressure vessel, allowing 100% access to waterside surfaces.  The tank will be accessible in the field through a 
manway sized opening, allowing access to 100% of interior surfaces.  All tank connection fittings will be nonferrous and 
removable from the tank.   
 
 

  

Tank Lining 

 
 

The tank will be a plated with electroless nickel (EN).  Plating will occur after the pressure vessel is completely 

fabricated and all welding is completed.  The EN plating will be a high-phosphorus (10%) and nonporous composition 
suitable for submersion service (ASTM B733 standard may be used as a guideline). For additional protection against 
galvanic corrosion, which may occur within the potable water system, the electroless nickel plating may have a high-
dielectric-strength polymer overcoat.   
 
The lined tank will not require sacrificial anode rods and none will be used

.  Water heaters that use anode rods in a 

vessel that contains non-ferrous heating surfaces will not be acceptable.

 

 
 
 

Burner and Venting 

 

 

Combustion will be provided by a forced-draft power burner with an oil train meeting the following agency 

requirement for the input specified: 
 
 

 

___ UL (standard) 

___ FM   

___ IRI   

___ Other ______________________ 

 

 

Burner will be configured to accept ____ room air _____ direct inlet combustion air.  

 

 

(continued) 