24
PX 181
Max. 14 of PX181s
PX 181
PX 181
Scheme connection of multiple panels PX181 and Px140 controller:
The panels should be connected on a serial basis, with the last panel being finished with a 120
Ω
terminal (insert a resistor with 120 Ω resistance between the positive pin and the negative pin).
Even if you want to connect just one PX181 panel to PX140, it is necessary to insert the
120
Ω terminal.
GND
terminator
(resistor 120 Ohm)
terminator
(resistor 120 Ohm)
For communication between PX140 and PX181 and also between touch panels connected in
series, use screened twisted pair cables with impedance of 120
, e.g.
• RS 485 LAPP UNITRONIC® LiYCY (TP) paired 2 x 2 x 0.14
• LI2Y(St)-CY 1x2x0,22mm2 120
For the purpose of connecting the device, you can also use a twist cable and, in that case,
you need to connect the white-and-orange colour of the cable as a plus (+), and the orange
colour as a minus (-); and the white-and-brown colour as the screen.
Ω
Ω
DMX OUT
REMOTE CONTROL
DMX IN
EXT CTRL
+
+
+
-
-
-
12-24V DC
+5 V input
12 1110 15 14 13
6
1
3
8
4 5
7
24
9
2
16 17 18 19 20 21
22 23
PX 140
Architectural
Lighting
Controller
USB LINK
DMX OK
POWER
www.pxm.pl
GND
GND GND GND
GND
GND
GND
+ -
GND GND GND
GND GND GND
GND GND
The view of the terminal block
on the back of the PX181 casing
cables between the controller
and the panel should be connected
in the correct order accordance
with the designations
EXT CTRL on PX 140
and PX 181: + to +, - to -
and GND to GND