Keep a minimum distance of 6 m to
a potential fire source.
f
Keep a minimum distance of 0.5 m to
surrounding walls, furniture and lamps.
Areas susceptible to draughts
For occurring smoke to be able to reach the
smoke alarm device, there may not be any
strong draughty influences around the instal
-
lation site (e.g. caused by air conditioner and
ventilation intakes, fans). In rooms with forced
ventilation, perforated ceilings that serve for
ventilation must be closed off within a radius
of 0.5 m around the alarm device.
The use of smoke alarm devices is gov-
erned by DIN 14676.
Minimum equipment
•
Bedrooms
•
Children’s bedroom
•
Guest room
•
Corridors that serve as escape routes
•
Stairwells of apartment buildings
Optimal equipment
•
All residential and hobby rooms
•
Heating and work spaces
•
Office or workroom
•
Cellar
•
Attic
Conditional equipment
•
In kitchens, smoke alarm devices must
only be installed when false alarms
(e.g., caused by steam) are excluded
Not recommended
•
Bathrooms are excluded from the in-
stallation of smoke alarm devices due
to the high development of steam
•
Exception: bathrooms with
washing machines and cabinets
4.1 Area to be monitored
Use a device if at least one of the follow-
ing applies:
•
Monitoring area less than 60 m
2
,
and ceiling height of less than 6 m
•
Ceiling panels (height lower
than 20 cm) with joists (ceiling
surface less than 36 m
2
)
Use additional equipment if at least one
of the following applies:
•
Monitoring area greater than 60 m
2
•
Ceiling height greater than 6 m
•
High partial walls
•
Separating pieces of furniture
•
Platform / gallery (area greater than
16 m², at least 2 m long and wide)
•
Ceiling panels (height greater
than 20 cm) with joists (ceiling
surface more than 36 m
2
)
In rooms with beams (e.g., wooden
beams), the number and arrange-
ment of the devices depends on
the height of the joists and the
surface formed by the beams.
4.2 Requirements for the
monitoring area
When selecting the appropriate monitor-
ing area, observe the following:
f
Position the device centrally on the ceiling.
f
Position master or shared radio group at
a central location (e.g., in the corridor).
f
Maintain an approximately equal
distance between the master and
other devices of a radio group.
f
Maintain an approximately equal
distance between the shared radio
group and other radio groups.
f
Install additional equipment if required.
f
Keep a minimum distance of 2 m to
electronic, radio-based devices
(e.g., wireless routers).
f
Keep a minimum distance of 3 m to
other radio smoke alarm device.