System Option 6. The system may be configured for use with the following:
Abort Digi Active High: This will switch from 0 to 12V at the Abort digi com output when the
panel is reset after an alarm activation if a code is entered before a 90 second time out
period.
Abort Digi Active Low: This will switch from 12 to 0V at the Abort digi com output when the
panel is reset after an alarm activation if a code is entered before a 90 second time out
period.
Open Digi Active High: This will switch from 0 to 12V at the Open digi com output when the
panel is Set or unset.
Open Digi Active Low: This will switch from 12 to 0V at the Open digi com output when the
panel is Set or unset.
Duress On / Off: If the last two digits of a user code are reversed when setting or unsetting
the alarm panel a duress code will be sent to the Central Receiving Station (if subscribed to).
System Options 7, The system may be configured for use with the following:
Alarm / P.A. / Fire / Confirmed Alarm restoral reporting on / off.
System Options 8, The system may be configured for use with the following:
Abort restoral reporting on /off.
System Options 11 to 20,
The system may be configured for use with the following:
In each set mode and in day mode, Alarm, P.A, Fire, Confirmed Alarm, Abort, Set/Unset and
System Faults can all be programmed as either ‘on or off’. If programmed as on, when
activated a signal will be sent to the Digi output to report this action and an event generated.
Reported system faults are, bell fuse failure, auxiliary fuse failure, battery missing, low battery
voltage, mains failure, line failure PC and line failure Digi.
System Option 21,
The system may be configured for use with the following:
Limited Reset:
Users can reset the panel after a keypad activated P.A or Fire alarm or a 24
hour zone alarm when in day mode, but an engineer code or anti code must
be entered after a zone alarm activation when in set mode. System option
1 must be configured for engineer only system reset or System Option 4
anti code reset.
All Resets:
After any alarm condition (P.A. Fire or zone) an engineer code or anti code
must be entered. System option 1 must be configured for engineer only
system reset or System Option 4 anti code reset.
Re-set omit:
If selected, any zone triggered in an alarm activation will be omitted after
the bell has timed out and the system reset.
No Re-set omit: If selected, any zone triggered in an alarm activation will remain protected
after the bell has timed out and the system reset.
Global Tamper Negative Return:
Upon the removal of0V the tamper alarm will be triggered.
Note: The TT terminals must be connected together.
Global Tamper Voltage Free Tamper Loop:
Upon opening the Loop between the TT terminals a tamper alarm will be
triggered.
Programmable Re-sets:
The number of control panel re-sets maybe programmed as follows:
a) from 1 to 9 to give up to 9 re-sets
or
b) 0 for continuous re-setting after an alarm activation.
Alarm Receiving Centre Telephone Number:
This is the telephone number of the central monitoring Station which, if required, the panel
will dial to during an alarm activation.
Page 16
Summary of Contents for ATLAS 8 PLUS
Page 9: ...Rins163 Issue 9 Page 9...
Page 19: ...Rins163 Issue 9 Page 19...
Page 25: ...Rins163 Issue 9 Page 25...
Page 37: ...Rins163 Issue 9 Page 37...
Page 45: ...Rins163 Issue 9 Page 45...
Page 47: ...Rins163 Issue 9 Page 47...
Page 68: ...ATLAS 8 PLUS SERVICE HISTORY Page 68...
Page 69: ...Rins163 Issue 9 Page 69...