4.2
Wiring
If the power ground terminal and the negative 4–20mA terminal in the controller are internally connected
(non-isolated 4–20mA input), it is unnecessary to connect the 4–20mA negative wire (green) to the 4–20mA
negative terminal in the controller. If a separate DC power supply other than that from the controller is used,
make sure that the output from the power supply is rated for 22–26 VDC @ 65mA.
*
NOTE
*
The negative 24V power terminal (power ground) and the negative 4–20mA ter-
minal on the LSP-X01 Series probe are internally connected.
Follow the wiring table below to connect the LSP-X01 Series probe to a controller:
Table 2.
Wire Color
Designation
Red
24V +
Black
24V Power ground
Brown
4–20mA +
Green
*
4–20mA -
Clear
Shield, earth ground
*
Internally connected to the power
ground
5
Instrument Overview
The indicators on the top of the sensor (Figure 6) are used to indicate power status and Bluetooth connec-
tion status.
Table 3.
LED Status
On
Off
Green LED
Power Supply is on
Power Supply is off
Blue LED
Bluetooth is connected
Bluetooth is disconnected
*
NOTE
*
The Bluetooth connected LED will illuminate within 30 seconds of powerup of the
device. This feature is designed to minimize controller power draw during startup.
Figure 6.
Sensor connection and indicators
LSP-X01 Series User Manual