Safety
I
08
[ Table 2-2 : Technical Specifications (Australia & New Zealand) ]
INVERTER (Derates > 40°C)
Battery (Derates outside these temperatures)
General Data
AC connection type
Nominal apparent power
Nominal AC voltage
Nominal frequency
AC Nominal Active Power / Max
Max. back-up port output short-circuit fault current (A)
Single phase
3000 VA
230 VAC
50 Hz
3000 W / 4600 W (10 min)
125 A, 4.384 ms
Back-up Output
Features
European efficiency
Max. efficiency
Protective Device
DC disconnection device for PV
Ground-fault monitoring / grid monitoring
95.5 %
96.2 %
Yes
Yes / Yes
Display
Communication
Energy management system
Certificates and approvals
Touch TFT LCD “4.95” inch
LAN (Modbus TCP / IP), RS485, CAN
Integrated
Island protection
Shifting the frequency of the INVERTER away from nominal
conditions in the absence of a reference frequency.
(Frequency shift)
Dimensions (W x H x D, mm)
Weight
Protective class (I, II, III)
Degree of protection
Max. permissible value for relative humidity
Operating temperature
Suggested operating temperature
Storage temperature
INVERTER topology
Noise emission
Intend to use
Wet condition
Pollution degree
Maximum altitude rating
467.6 x 721.6 x 212.5 (INVERTER)
467.6 x 721.6 x 212.5 (Battery)
31.28 kg (INVERTER)
52.26 kg (4 kWh) / 59.36 kg (6.3 kWh)
Class I
IP 65 (Both)
4% to 100 % (Condensing)
-20 - +50 °C
+0 - +40 °C (4 kWh) / -10 - +40 °C (6.3 kWh)
+0 - +40 °C
-20 - +60 °C (Both)
Non-Isolated
≤ 40 dB(A) @ 1m
Outdoor
Yes
3
< 2000 m
Efficiency (PV to Grid)
Rated / Maximum input apparent power
Rated / Maximum input active power
Rated input voltage
Rated / Maximum continuous input current
Rated input frequency
Max. grid port input short-circuit fault current (A)
3000 / 4000 VA
3000 / 4600 W
230 Va.c.
13/25 Aa.c.
50 Hz
56.5 A (191.048 ms)
Grid Input
IEC 62109-1/2, AS 62040.1.1, AS/NZS 4777.2,
IEC 62116, IEC 60068-2-52 (INVERTER)
IEC 62619, IEC 62040-1, IEC60068-2-52 (Battery)