WEB Display
HMI Display
Description
Measures
The product stops the generating process
because a significant protection event has
occurred. Wait until the event message
disappears. After the event message is
removed, it automatically returns to normal.
If it is not removed until the time limit is
reached, it is converted to a significant event.
BAT4 Discharge Over
Current Protection
BAT4 DCHG
OC P
B32P
The product stops the generating process
because a significant protection event has
occurred. Wait until the event message
disappears. After the event message is
removed, it automatically returns to normal.
If it is not removed until the time limit is
reached, it is converted to a significant event.
BAT4 Charge Over
Current Protection
BAT4 CHG OC
P
B31P
Power reset of the system is required. If the
symptom still occurs after reset, repair of
BMS or PCS Control Board is necessary.
BAT4 Cell Voltage
Sensing Data Hold
Protection
BAT4 CEL V
HOLD P
B33P
When the maximum cell or rack voltage is
above protection level, thus terminating the
system. Automatically returns to normal when
the maximum cell or rack voltage goes below
the limit value.
BAT4 Cell or Rack
Over Voltage Protection
BAT4 CEL OV
P
B34P
When the minimum cell or rack voltage is
below protection level, thus terminating the
system. Automatically returns to normal when
the minimum cell or rack voltage goes above
the limit value.
BAT4 Cell or Rack
Under Voltage
Protection
BAT4 CEL UV
P
B35P
When the maximum cell temperature is above
protection level, thus terminating the system.
Automatically returns to normal when the
maximum cell temperature goes below
the limit value
BAT4 Cell Over Temp
Protection
BAT4 CEL OT
P
B36P
97
I
Problem Confirmation