background image

8

9

INSTALLATION AND OPERATION MANUAL SOLAR MODULES Q.PEAK DUO XL-G9.3 / BFG AND XL-G9.3 / BGT – Q CELLS

INSTALLATION AND OPERATION MANUAL SOLAR MODULES Q.PEAK DUO XL-G9.3 / BFG AND XL-G9.3 / BGT– Q CELLS

Fig. 2: 

Installation options for crystalline Q CELLS modules. All dimensions are given in inch (mm in brackets). Also observe 
the maximum test loads and clamping range as specified on page 9.  
The illustrated installation options apply for both horizontal and vertical module orientation. 

 

Module 

Clamp 

Subconstruction 

Mounting profile

2  PLANNING

2.3  MOUNTING OPTIONS

TYPE OF 
INSTALLATION

POINT MOUNTING SYSTEM

LINEAR MOUNTING SYSTEM

INSTALLATION 
WITH CLAMPS

INSTALLATION  
ON MOUNTING  
POINTS

FB1

4 × mounting 
slots

16.8
(427.5)

CL1a

11.8-21.6

(300-550)

CL3

11.8-21.7

(300 - 550)

FB2

4 × mounting 
slots

16.8

(427.5)

Specifications

MOUNTING  
OPTION

POSITION OF CLAMPS

1

 [IN (MM)]

TEST LOAD  
PUSH/PULL

[PA]

DESIGN LOAD 
PUSH/PULL

[PA]

SAFETY  
FACTOR

CL1a

11.8 - 21.6 (300 - 550)

3600 / 2865

2400 / 1910

1.5

CL3

FB1

16.8 (427.5)

3600 /3000

2400 / 2000

FB2

1

 

2

Distance between outer edge of module and middle of the clamp (see table „2.3 Mounting Options“ on page 8). 

Loads according to IEC 61215-2:2016 and UL 61730.

ATTENTION

 

Ä

The loads in the table are related to the mechanical stability of the solar modules. The mechanical stability of the mounting system 
including clamps, screws, washers etc. has to be evaluated by the system supplier. The listed test load values for Q CELLS were 
determined with the following clamp parameters: clamp width = 1.58 in (40 mm) and clamp depth = 0.39 in (10 mm). The system 
installer is responsible for the determination of location-specific load requirements.

 

Ä

Ensure, that the subconstruction does not touch the junction box (even under load). The clamps or insertion profiles etc. do not 
touch the glass (even under load).

 

Ä

Ensure, that the connection cables of the junction box do not run between the laminate and mounting rails.

 

Ä

A minimum support depth of 0.59 in (15 mm) is required on the back side of the module.

 

Ä

For CL1a and CL3 with rails: Ensure that module frame is fixed directly on the rail of the substructure (no spacer allowed between 
the module and mounting rail).

 

Ä

The module bends under loads. Therefore, sharp objects (e.g. screws) must not be mounted near the module backside.

 

Ä

Use M8 corrosion-proof screws and washers (diameter ≥ 15.8 mm or ≥ 0.62 in). Mounting screws and washers should have the 
same material properties.

 

Ä

For CL1a and FB1: These mounting options are not recommended as mounting rails will cast shade on the module rear side.

2  PLANNING

2.3  MOUNTING OPTIONS

Summary of Contents for Q.PEAK DUO XL-G9.3 / BFG

Page 1: ...Valid for North America INSTALLATION AND OPERATION MANUAL Q PEAK DUO XL G9 3 BFG and XL G9 3 BGT solar modules...

Page 2: ...operator are responsible for com pliance with all applicable statutory requirements and regulations The following regulations and standards must be upheld at all times during the installation operati...

Page 3: ...e documents This installation manual is only valid in combination with the following technical information DOCUMENT TYPE Product data sheet Packaging and transport information MISUSE OR INCORRECT USE...

Page 4: ...to 185 F Pull loads and push loads according to chapter 2 3 Mounting Options Test Load in accordance with IEC 61215 and Design Load 1 5 in accordance with UL 61730 Installation using a mounting struct...

Page 5: ...NTION The loads in the table are related to the mechanical stability of the solar modules The mechanical stability of the mounting system including clamps screws washers etc has to be evaluated by the...

Page 6: ...unt when deter mining the maximum number of modules in the string Parallel Connection Modules may be damaged by the occurrence of reverse currents caused by module defects ground leaks or defective in...

Page 7: ...rizontally as shown NOTE Module damage may occur Never step on modules Do not subject modules to any mechanical stress Do not allow any objects to fall onto modules 3 INSTALLATION 3 1 SAFETY AND TRANS...

Page 8: ...lt from the separation of a closed circuit These can result in life threatening injuries The danger increases when several modules are connected in series Please be aware of that the entire open circu...

Page 9: ...DANGER Risk of fatal injury due to electric shock Electrical work may only be performed by qualified and skilled personnel see page 3 Ensure correct polarity Use solar cables for the connection at the...

Page 10: ...The U S National Electrical Code addresses these issues in Article 250 Proper grounding is achieved by bonding all exposed non current carrying metal equipment to the appropriately sized equipment gro...

Page 11: ...t Grounding Conductor Aluminum Frame Screw Stainless Steel Q CELLS solar modules are known for a long operating life and minimal maintenance effort and expense Dirt and grime are usually washed away b...

Page 12: ...trum Center Drive Suite 1400 Irvine CA 92618 USA TEL 1 949 748 59 69 EMAIL inquiry us q cells com WEB www q cells us Subject to change without notice Q CELLS Installation manual solar modules Q PEAK D...

Reviews: