53
System Settings
3
Volt-Watt P(V)
AU
The inverter changes the maximum input·output active power depending on system voltage. The
inverter responds in two ways depending on charging or discharging operation.
•
During charging operation
: If frequency decreases
below V
W2_CH
, it decreases input active power, and it
does not exceed the designated active power input
constraint W1 below V
W1_CH
.
PO
WER INPUT
, P /P (%)
char
ge
rat
ed-ch
0
10
20
30
40
50
60
70
80
90
100
V
W1-ch
V
W2-ch
INVERTER VOLTAGE, V
•
Discharging mode
: It decreases input active power
from the frequency of V
W1
, and it does not exceed the
designated active power output constraint W4 above
V
W2
.
M
AXIMUM POE
WR LE
VER
, P
/S (%)
ra
te
d
0
20
40
60
80
100
120
V
W1
V
W2
INVERTER VOLTAGE, V
Parameter
Default Values of Volt-Watt Response
Range
Australia A
Australia B
Australia C
New Zealand
W1 [%]
20
0
20
20
0 to 20
V
W1_CH
[V]
207
195
207
216
180 to 230
V
W2_CH
[V]
215
215
215
224
180 to 230
V
W1
[V]
253
250
253
242
235 to 255
V
W2
[V]
260
260
260
250
240 to 265
W4 [V]
20
20
20
20
0 to 20
•
W1 [%]
: Inverter maximum active power Input level below VW1_CH
•
V
W1_CH
[V]
: Voltage where power input level is W1
•
V
W2_CH
[V]
: Lower limit of continuous operation range
•
V
W1
[V]
: Upper limit of the continuous operation range
•
V
W2
[V]
: Voltage where power output level is W4
•
W4 [V]
: Inverter maximum active power output level above VW2
4
Fixed Power factor
AU
The setting range for the fixed power factor mode is 0.8 to 1.0 and supplying and absorbing can be
set for reactive power. The default power factor is set to 1.0.
5
Fixed Q (Reactive power mode)
AU
The reactive power mode outputs reactive power in the fixed rate for apparent power. The minimum
setting range for the reactive power (vars) rate for apparent power is 60 % or higher from 60 %
absorption to 60 % supply, and the default reactive power is set to 0 %.