4 Electrical connection

4.2 Electrical installation safety

Danger! Risk of fatal injury due to electric shock!

  Be sure to maintain the time intervals as specified by 

the inverter manufacturer between switching off the 

inverter and beginning any further work.

Danger! Risk of fatal injury due to electric shock!

  Never plug or unplug the cable when under load. 

Modules must not carry any current.

1. Switch off the inverter.

OFF

EN

2. Switch off the DC circuit breaker.
3.  Measure shutdown in DC String. 

(no DC current flow).

4.  Disconnect plugs by the use of appropriate 

and qualified tools of the manufacturer.

5.  When connecting the modules proceed in reverse 

order.

Danger! Risk of fatal injury due to electric shock!

  Electrical work may only be performed by qualified 

and skilled personnel (see page 3).

  Ensure correct polarity.

4 Electrical connection

4.3 Connection of modules

  Use solar cables for the connection at the junction 

box outlet.

  Only interconnect connectors of the same type and 

manufacturer.

  Use minimum 4 mm

2

 copper wires insulated for a 

minimum of 90 °C for field connections.

Note! Module damage may occur!

  Ensure that the cabling is not under mechanical stress 

(Comply with bending radius of ≥ 60 mm).

  Ensure that the cables do not run between module 

and mounting rail or structure (danger of pinch).

  Ensure for a tight connection between the plugs. 

Plugs click together audibly.

EN

click

Danger! Risk of fatal injury due to electric shock!

  Ensure that all electrical components are in a proper, 

dry, and safe condition.

  To avoid complex cabling arrangements, it is often 

advantageous to rotate some modules 180°.

  Module orientation can clearly be identified from the 

front side by the serial number and barcode labelled 

behind the module glass on the side with negative 

connection cable.

SOLAR

EN

Inverter

180°

180°

  Do not connect modules with different orientations or 

angles of inclination in the same string.

Summary of Contents for Q.PEAK DUO ML-G11 Series

Page 1: ...Installation and operation manual Q PEAK DUO ML G11 X solar module series...

Page 2: ...e of the solar modules This manual Other applicable stipulations such as country specific regulations for pressure equipment operational safety hazardous goods and environmental protection Regulations...

Page 3: ...n MISUSE OR INCORRECT USE OF SOLAR MODULES VOIDS THE LIMITED WARRANTY AND MAY CREATE A SAFETY HAZARD AND RISK PROPERTY DAMAGE THIS INCLUDES IMPROPER INSTALLATION OR CONFIGURATION IMPROPER MAINTENANCE...

Page 4: ...ind loads Properly fastened to the ground the roof or the fa ade Forces acting on the module are relayed to the mounting substructure Ensures sufficient rear ventilation of the module Avoid the usage...

Page 5: ...m supplier The listed test load values have been determined with the following clamp parameters clamp width 40mm and clamp depth 10mm The system installer is responsible for the determination of locat...

Page 6: ...y be damaged by the occurrence of reverse currents caused by module defects ground leaks or defective insulation Ensure that the maximum reverse current load capacity indicated in the data sheet is me...

Page 7: ...ght and horizontally as shown Note Module damage may occur Never step on modules Do not subject modules to any mechanical stress Do not allow any objects to fall onto modules 3 Installation 3 2 Prepar...

Page 8: ...ectric arcs may result from the separation of a closed circuit These can result in life threatening injuries The danger increases when several modules are connected in series Please be aware of that t...

Page 9: ...el see page 3 Ensure correct polarity 4 Electrical connection 4 3 Connection of modules Use solar cables for the connection at the junction box outlet Only interconnect connectors of the same type and...

Page 10: ...ulations Warning Fire Risk Do not use light concentrators e g mirrors or lenses Ensure that the cabling is not exposed and or hanging and is protected from dirt moisture and mechanical friction 5 Grou...

Page 11: ...may occur Remove snow and ice carefully without force e g with a very soft broom Do not scratch off dirt Module cleaning has to be done by qualified personnel according to the state of the art and tak...

Page 12: ...n manual solar modules Q PEAK_DUO_ML G11 X_modules_series_2022 06_Rev02_EN HANWHA Q CELLS GMBH OT Thalheim Sonnenallee 17 21 06766 Bitterfeld Wolfen Germany EMAIL WEB TEL FAX sales qcells com www qcel...

Reviews: