Installation
23
All connections for communications and power are located on the rear panel of the
ePAQ. The Maintenance Port is located on the front panel.
6.2 Power Connections
Refer to Figure 6.4 for power wiring. Refer to Section 1: General Specifications
for specific power details.
Power inputs are on the H/+ (AC Hot / DC Positive) and L/- (AC Neutral / DC
Negative) of the POWER Terminal Block. The terminal block is a barrier type
terminal block. Use #14 AWG wire for AC or DC power inputs with Panduit (or
equivalent) P/N PV14-8F-C spade terminal.
The EGND terminal is for the ground connection. It is important that the ground
connection is made and is in working condition. This is the chassis ground for
the unit.
WARNING
Before applying power to the ePAQ, make certain that the power and ground
connections are made to the correct terminals and that they are secure. Failure
to do so may result in unit damage or personal injury.
NOTE
Be sure that the power input wires are routed away from any communications
cabling to prevent noise interference.
Figure 6.4 -- Power Connections
6.3 Communications Interface Terminations
Refer to Figures 6.5 thru 6.9 for specific communication interface connection
information. Refer to Section 1: General Specifications for port ratings.
6.3.1
Port 4 (RS-232)
This port is included in all possible ePAQ configurations and is always a RS-232
port. It is suitable for use to connect to radios, external modems or fiber optic