UG-1084
ePAQ-9405
User’s Guide
Copyright © 2017 QEI
Test Panel
35
15.13 Displaying Dip Switch States (DIP)
A test panel command is available for examining the state of the 16 dipswitches on
the ePAQ. Type
DIP
<enter> from the test panel. Dip switches are displayed in the
order that they appear on the front panel.
Example:
DIP <enter>
Display:
ePAQ-9405_A> DIP
00010110 00001100
ADD-A. ADD-B.
15.14 Displaying the Software Version (VER)
To display the version of software residing in the ePAQ, type
VER
<enter>.
Example
VER <enter>
Display
QEI ePAQ-9405 Link:80-013XXX-XXX 3/22/16 Chksum: 6320d4ca
15.15 TP Command
This command invokes a software monitor, which is useful in diagnosing different
types of problems.
Example
Type TP 15 <enter>
Display
Software Monitor running at level 15
The ePAQ will print error and informational messages (if any) on the test panel, while
in operation.
15.16 SOE Command
This command allows saved SOE events to be viewed.
SOE <[point number]> <count>
SOE events are displayed most recent first, in the following format:
soe
52 events available (in Ram)