UG-1084
ePAQ-9405
User’s Guide
Copyright © 2017 QEI
Specifications
3
Input Current
Approx. 4 mA per point
Protection
Optically coupled, 1500 VDC between inputs and logic common
Surge Withstand to IEEE 37.90.1 SWC
Indication
One LED per status input point, input is on when lit.
Connector
Three (3) 12-pin terminal blocks (TB3A, TB3B, TB3C)
Status Keying Source
Connector
TB3C, pins 9,10 = (+); pins 11,12= (-)
Options
Important: See ordering information and “Keying Source”
section elsewhere in this guide.
Analog Point Interface
Addressability
4 points
Scaling options
0-1mA, 0-20mA, 0-5Vdc
Power Input
Voltage
12,24,48,125VDC. 120/240/277VAC (Note 1)
Current
18VA max.
Connector
6-pin terminal block (TB1)
Note 1: 277VAC Tol +/- 5% Max; Other /- 10%
Environment
Temperature
-40 to +85
o
C
Humidity
5 to 95% @ +70
o
C, non-condensing
Physical Dimensions
Mounting Dimensions
17.3” W x 3.5” H x 5.0” D without mounting brackets
19.0” W x 3.5” H x 5.0” D w/ rack mounting brackets