5)  Smell for gas, including near the floor

.  

If you smell gas, STOP!

  

Follow “B” in the safety  

        information above on this label.  If you don’t smell gas, go to the next step. 
6)  Turn on all electric power to the appliance. 
7)  Set thermostat to the desired setting. 
8)  Once the system is lit, inspect the entire installation. 
9)  Make sure the pressure in the boiler is stable. 
10)  Test both 4006A high limits by lowering their set points below the temperature of the boiler one at a time.  
 

If either aquastat fails to shut the burner down replace it immediately. 

11)  Simulate a loss of fuel by shutting the oil valve.  Once the valve is closed the burner should go into post –
 

purge and then lockout.   

12) Reset the burner before turning the oil back on to simulate ignition failure.  After ignition failure the 
 

burner should go through a purge period and then lookout. 

13)  Open the oil valve and return the burner to operation.  While the burner is running, trip the breaker at the 
 

panel, that should disable the burner and all other heating controls. 

14) Once it is determined that the system is operating properly, proceed to tuning up the burner using the 
 

proper instruments.  If you do not have any instruments, do not place this unit in operation until you have a 

 

competent burner technician tune up the burner. 

 

5. System Start-up Cont. 

19 

 

Recommended procedures for safety inspection of an appliance should be in accordance with the 

National Fuel Gas Code, ANSI Z223.1. The following procedure will help evaluate the venting system. It is 
intended as a guide to aid in determining that the venting system is properly installed and is in a safe condition 
for continuous use. This procedure should be recognized as a generalized procedure which cannot anticipate all 
situations. Accordingly, in some cases, deviation from this procedure may be necessary to determine safe 
operation of the equipment. If it is determined that a condition exists which could result in unsafe operation, 
the appliance should be shut off and the owner advised of the unsafe condition. Corrections must be made 
before the appliance is put into continuous operation. The following steps should be followed in making a 
safety inspection. 
   1.   Visually inspect the venting system for proper size and determine that there is no  
 

 flue gas spillage, blockage, restriction, leakage, corrosion, or other deficiency which could cause an 
unsafe operation. 

   2.   Place in operation the appliance being inspected. Follow the lighting instructions and  
 

 adjust thermostat so appliance will operate continuously. 

   3.   Determine that the burner is operating properly and that the burner ignition operates  
 

 satisfactorily by interrupting and re-establishing the electrical power of the appliance 

 

 in any convenient manner. Test the burner safety device to determine if it is operating 

 

 properly by disconnecting the flame safety circuit. 

   4.   Test for smoke spillage at the burner inlet air location around the VRV after 5 minutes of operation. Use 

a draft gauge, flame of a match or candle, or smoke from a cigarette, cigar or pipe. Shut off appliance 
thermostat and check for spillage around the VRV. If a flow reversal is noticed, house depressurization 
is occurring and make up air is required. 

Once installation is complete, check the boiler with instruments to ensure that it is working properly. 

6. Installation Inspection

 

Summary of Contents for Air Compressor

Page 1: ...nd service must be performed by a qualified installer service agency or the gas supplier Please Read Instructions Carefully Save for Future Reference QUINCY HYDRONIC TECHNOLOGY INC 3560 LAFAYETTE RD P...

Page 2: ......

Page 3: ...5 Vent System Installation 2 6 External Clearances 6 Clearances to Combustibles 7 DVH 5 System 2 1 8 Installation of Make up Air 2 2 9 Burner Setup Installations 3 10 B 10 Burner Setup 3 1 11 SG Burne...

Page 4: ...he literature and warranties supplied by the manufacturers of the various accessory equipment This equipment is warranted by the respective manufacturers not by Quincy Hydronic Technologies Inc Each p...

Page 5: ...the boiler If the manual is no longer legible contact QHT I NC for a new manual After the boiler is installed and in working order it should be serviced once a year before each heating season Service...

Page 6: ...son A victim may not experience any symptoms only one symptom or a few symptoms Suspect the presence of carbon monoxide if symptoms tend to disappear when you leave your home The following signs may i...

Page 7: ...plication The last piece of the complete package is a direct vent specific burner The Direct Vent Systems are a non powered positive pressure vent hood system for gas or oil fired appliances that prov...

Page 8: ...Hood D 5 CONHOOD 3 4 90 Light Gauge Elbow D 4 ELB 11 5 X 2 Insulation Sleeve for Exhaust Hood Elbow D INSULSLEEVE 4 4 X 8 Aluminum Flex Duct D 4 ALUFLEX 12 1 x x 1 Bull Head Tee D 1006010 5 6 90 Vent...

Page 9: ...grade when located adjacent to public walkway 6 The Vent hood shall be located so that flue gasses are not directed to jeopardize people overheat combustible structures materials or enter buildings 7...

Page 10: ...ust be ducted directly to the burner through the hood unit supplied The Direct Vent System must be gas tight CLEARANCES TO COMBUSTIBLES SYSTEM OPERATING TEMP Clearance Sealant Required Vent Kit Horizo...

Page 11: ...determined cut a 7 1 2 hole through the wall for the vent terminal Using 2 X 2 Frame a box around the hole on the outside of the house so the flange is mounted away from the siding Attach the hood to...

Page 12: ...labeling right side up and perfectly horizontal 7 Off of the last leg of the tee install the 4 duct elbow and then the aluminum flex pipe 8 Finally attach the other end of the flex pipe to the intake...

Page 13: ...and electrodes by the book using the manufacturer s gauges 2 Installing a quality micron filter at the burner 3 Making careful tight flare connections without couplings on oil suction line 4 Checking...

Page 14: ...lid Solid Semi Solid Hollow Pump Pressure 200 200 150 190 Head Setting 1 1 1 3 75 Air Setting 0 9 5 16 5 6 120mm Fan Needed BURNER MANUFACTURER Beckett AFII 150 NEC 301 302 303 NX NEC 1101 1102 1103 B...

Page 15: ...P 2 KA Firing Rate 65 1 00 1 30 Insertion Depth 3 5 3 5 3 5 Nozzle 0 5 X 80 0 75 X 70 1 00 X 80 Spray Pattern solid solid Semi Solid Pump Pressure 200 200 200 Head Setting 6 3 3 Air Setting 12 0 11 5...

Page 16: ...trically bonded to ground in accordance with the requirements of the authority having jurisdiction or in the absence of such re quirements with the National Electrical Code ANSI NFPA 70 or Canadian El...

Page 17: ...OCAL CODES LO WATER CUTOFF FIRE O MATIC SR 301 T 1 T T 2 T T 3 T GND L1 N L2 N L3 N L2 CF L1 X1 X2 L1 HOT L2 NEUTRAL 120 VAC 15 AMP Breaker ON OFF SWITCH G W R B G W R B L 4006A Postpurge safety limit...

Page 18: ...AL CODES LO WATER CUTOFF FIRE O MATIC SR 301 T 1 T T 2 T T 3 T GND L1 N L2 N L3 N L2 CF L1 X1 X2 L1 HOT L2 NEUTRAL 120 VAC 15 AMP Breaker G W R B G W R B L 4006A N X ALARM L G Ground on Riello Chassis...

Page 19: ...4 Wiring 16 Riello Burner with post purge control multi zone control wiring...

Page 20: ...OCAL CODES LO WATER CUTOFF FIRE O MATIC SR 301 T 1 T T 2 T T 3 T GND L1 N L2 N L3 N L2 CF L1 X1 X2 L1 HOT L2 NEUTRAL 120 VAC 15 AMP Breaker ON OFF SWITCH G W R B G W R B L 4006A Postpurge safety limit...

Page 21: ...ly lights the burner Do not try to light the burner by hand A BEFORE OPERATING smell all around the appliance area for gas Be sure to smell next to the floor because some gas is heavier than air and w...

Page 22: ...ng system is properly installed and is in a safe condition for continuous use This procedure should be recognized as a generalized procedure which cannot anticipate all situations Accordingly in some...

Page 23: ...ions and leak ages Repair any problems that are found in accordance with local or national codes Failure to repair leakages can result with CO Carbon Monoxide Poising which can lead to death 7 Disconn...

Reviews: