background image

20 

7. Service & Maintenance 

In order to ensure that the boiler is operating properly, it should be inspected annually at the 
beginning of the heating season by a qualified service technician.  Failure to do regular 
maintenance on the boiler, could result in a loss of system efficiency as well as equipment 
failure. 
 
1)  Turn off all electrical power to the boiler before servicing any part of the boiler. 
2)  During the inspection process, the technician should inspect and correct problems that 

the owner has noted.   

3)  Check the area around the boiler to ensure that no combustibles are in the area. 
4)  Remove any obstruction from the ventilation and combustion air openings to the boiler 

room.  Check to ensure that the openings are open. 

5)  Check the boiler vent discharge and air intake to ensure that they are unobstructed.  If 

obstructions exist, remove.  

6)  Visually check the entire flue gas venting system for blockages, deteriorations and leak-

ages.  Repair any problems that are found in accordance with local or national codes.  
( Failure to repair leakages can result with CO (Carbon Monoxide) Poising which can 
lead to death.) 

7)  Disconnect vent pipe from the breeching and remove front upper and lower door.  Use a 

light to inspect the boiler heating surfaces.  If signs of soot are showing, clean boiler 
heating surfaces with a wire brush and vacuum any debris in the boiler. 

8)  Reconnect the vent pipe to the breeching.  Put silicon back onto the joint and tighten the 

clamps before re-commissioning the boiler. 

9)  With the power to the boiler still off, remove the burner and follow manufactures in-

structions for cleaning. 

10) Before putting burner back onto the boiler,  check the insulation on the door.  If the insu-

lation is damaged or displaced, do not operate the boiler until the insulation has been re-
paired or replaced.  (Failure to replace damaged insulation can result in a fire hazard and 
can cause personal injury or death, and can cause substantial property damage.) 

11) Return the boiler to normal operation and check all controls before leaving the job. 

Summary of Contents for Air Compressor

Page 1: ...nd service must be performed by a qualified installer service agency or the gas supplier Please Read Instructions Carefully Save for Future Reference QUINCY HYDRONIC TECHNOLOGY INC 3560 LAFAYETTE RD P...

Page 2: ......

Page 3: ...5 Vent System Installation 2 6 External Clearances 6 Clearances to Combustibles 7 DVH 5 System 2 1 8 Installation of Make up Air 2 2 9 Burner Setup Installations 3 10 B 10 Burner Setup 3 1 11 SG Burne...

Page 4: ...he literature and warranties supplied by the manufacturers of the various accessory equipment This equipment is warranted by the respective manufacturers not by Quincy Hydronic Technologies Inc Each p...

Page 5: ...the boiler If the manual is no longer legible contact QHT I NC for a new manual After the boiler is installed and in working order it should be serviced once a year before each heating season Service...

Page 6: ...son A victim may not experience any symptoms only one symptom or a few symptoms Suspect the presence of carbon monoxide if symptoms tend to disappear when you leave your home The following signs may i...

Page 7: ...plication The last piece of the complete package is a direct vent specific burner The Direct Vent Systems are a non powered positive pressure vent hood system for gas or oil fired appliances that prov...

Page 8: ...Hood D 5 CONHOOD 3 4 90 Light Gauge Elbow D 4 ELB 11 5 X 2 Insulation Sleeve for Exhaust Hood Elbow D INSULSLEEVE 4 4 X 8 Aluminum Flex Duct D 4 ALUFLEX 12 1 x x 1 Bull Head Tee D 1006010 5 6 90 Vent...

Page 9: ...grade when located adjacent to public walkway 6 The Vent hood shall be located so that flue gasses are not directed to jeopardize people overheat combustible structures materials or enter buildings 7...

Page 10: ...ust be ducted directly to the burner through the hood unit supplied The Direct Vent System must be gas tight CLEARANCES TO COMBUSTIBLES SYSTEM OPERATING TEMP Clearance Sealant Required Vent Kit Horizo...

Page 11: ...determined cut a 7 1 2 hole through the wall for the vent terminal Using 2 X 2 Frame a box around the hole on the outside of the house so the flange is mounted away from the siding Attach the hood to...

Page 12: ...labeling right side up and perfectly horizontal 7 Off of the last leg of the tee install the 4 duct elbow and then the aluminum flex pipe 8 Finally attach the other end of the flex pipe to the intake...

Page 13: ...and electrodes by the book using the manufacturer s gauges 2 Installing a quality micron filter at the burner 3 Making careful tight flare connections without couplings on oil suction line 4 Checking...

Page 14: ...lid Solid Semi Solid Hollow Pump Pressure 200 200 150 190 Head Setting 1 1 1 3 75 Air Setting 0 9 5 16 5 6 120mm Fan Needed BURNER MANUFACTURER Beckett AFII 150 NEC 301 302 303 NX NEC 1101 1102 1103 B...

Page 15: ...P 2 KA Firing Rate 65 1 00 1 30 Insertion Depth 3 5 3 5 3 5 Nozzle 0 5 X 80 0 75 X 70 1 00 X 80 Spray Pattern solid solid Semi Solid Pump Pressure 200 200 200 Head Setting 6 3 3 Air Setting 12 0 11 5...

Page 16: ...trically bonded to ground in accordance with the requirements of the authority having jurisdiction or in the absence of such re quirements with the National Electrical Code ANSI NFPA 70 or Canadian El...

Page 17: ...OCAL CODES LO WATER CUTOFF FIRE O MATIC SR 301 T 1 T T 2 T T 3 T GND L1 N L2 N L3 N L2 CF L1 X1 X2 L1 HOT L2 NEUTRAL 120 VAC 15 AMP Breaker ON OFF SWITCH G W R B G W R B L 4006A Postpurge safety limit...

Page 18: ...AL CODES LO WATER CUTOFF FIRE O MATIC SR 301 T 1 T T 2 T T 3 T GND L1 N L2 N L3 N L2 CF L1 X1 X2 L1 HOT L2 NEUTRAL 120 VAC 15 AMP Breaker G W R B G W R B L 4006A N X ALARM L G Ground on Riello Chassis...

Page 19: ...4 Wiring 16 Riello Burner with post purge control multi zone control wiring...

Page 20: ...OCAL CODES LO WATER CUTOFF FIRE O MATIC SR 301 T 1 T T 2 T T 3 T GND L1 N L2 N L3 N L2 CF L1 X1 X2 L1 HOT L2 NEUTRAL 120 VAC 15 AMP Breaker ON OFF SWITCH G W R B G W R B L 4006A Postpurge safety limit...

Page 21: ...ly lights the burner Do not try to light the burner by hand A BEFORE OPERATING smell all around the appliance area for gas Be sure to smell next to the floor because some gas is heavier than air and w...

Page 22: ...ng system is properly installed and is in a safe condition for continuous use This procedure should be recognized as a generalized procedure which cannot anticipate all situations Accordingly in some...

Page 23: ...ions and leak ages Repair any problems that are found in accordance with local or national codes Failure to repair leakages can result with CO Carbon Monoxide Poising which can lead to death 7 Disconn...

Reviews: