67
B. The fan can choose two operating modes: high wind and low wind.
C. Humidity setting button cannot be pressed in fan mode
5.
Full water protection:
A. When the full water lasts for 3 seconds , the controller stops working and all
outputs are turned off. The full water indicator is on (FULL, the buzzer sounds 15
rings. Press any key, the bee The alarm will stop immediately.
B. When the full water fault is removed, the original machine’s operating status is
restored (the compressor must be protected by 3 minutes)
6.
Defrost function:
A. When it is in defrosting, the compressor is turned off, the fan is defrosted by high
winds, and the defrost indicator lights up (DEF).
B. When the room temperature is less than or equal to 16°C, the temperature of the
coil is not detected. According to the room temperature action, it is as follows:
Room temperature <5°C, the controller stops.
When 5°C ≤ room temperature ≤ 12°C, the compressor is running for 30 minutes
and the defrost is stopped for 10 minutes.
When 12°C< room temperature ≤ 16°C, the compressor is running for 45 minutes
and the defrost is stopped for 10 minutes
C. When the room temperature is greater than 16°C, the temperature of the coil
is detected, and the operation is performed according to the temperature of
the coil, as follows: When the compressor is running for 30 minutes, the coil
temperature is detected. If the coil temperature is ≤ 1°C, the defrosting is stopped
for 10 minutes.
7.
Compressor delay protection:
A. Every time the boot compressor is allowed to start immediately.
B. After the compressor is shut down, start it again, with at least a 3-minute interval.
WATER DRAINAGE
When the drainage tank is full, the tank full indicator light will turn on, the operation will
stop automatically and the buzzer will beep 15 times to alert the user, that the water need
to be emptied from the drainage tank.
EMPTY TANK
1.
Gently press on the sides of the tank and pull the tank out with both hands.