After the autoconfiguration is complete, check that all drops and modules have been
found. Select
Automation Network/View Configuration Files
and click
AN-X2-MOD-MAS RIO Network Configuration File
.
Example:
;QTS AN-X2 MOD RIO Scan Configuration Utility
;Copyright (c) 2005 Quest Technical Solutions
;Auto Config Mod I/O File
Drop=1,
;HoldTime=3, ; Drop Hold Time (x100ms, Default=3)
,Rack=1,
,,Slot=1,Type=B810,;Addr=d1s1,Inp=00,Out=01,8-OUT ISO B810
,,Slot=2,Type=B863,;Addr=d1s2,Inp=08,Out=00,REG 4 CH IN B863
,,Slot=4,Type=B804,;Addr=d1s4,Inp=00,Out=02,16-OUT B804
EndDrop
Drop=2,
;HoldTime=3, ; Drop Hold Time (x100ms, Default=3)
,Rack=1,
,,Slot=1,Type=CPS_114_xx,;Addr=d2s1,Inp=00,Out=00,AC PS 115/230V 10A
,,Slot=2,Type=CRP_93x_00,;Addr=d2s2,Inp=00,Out=00,RIO HEAD S908
,,Slot=3,Type=DDI_353_00,;Addr=d2s3,Inp=04,Out=00,DC IN 24V 4x8 Sink
,,Slot=4,Type=DDO_353_00,;Addr=d2s4,Inp=00,Out=04,DC OUT 24V 4x8
,,,,CfgLen=2,0x0000,0x0000
,,Slot=5,Type=ACO_020_00,;Addr=d2s5,Inp=00,Out=08,AN OUT 4CH CURR
,,,,CfgLen=6,0x8001,0x5555,0x0000,0x0000,0x0000,0x0000
,,Slot=6,Type=ACI_030_00,;Addr=d2s6,Inp=18,Out=00,AN IN 8CH UNIPOLAR
,,,,CfgLen=1,0x0001
EndDrop
When AN-X creates a configuration file, it includes comments in the file it creates, based
on the information in its module database. If you edit the automatically generated
configuration file, edit the comments as well.
See page 25 for information on how to transfer the configuration from AN-X and save it
to a file.