AN-X2-MOD-MAS Page
23
3. Click the
Send File To AN-X
button to send the file to AN-X.
AN-X parses the file and shows either the current configuration if configuration was sent
successfully or an error message if there was a problem with the file.
Configuration File Contents
The I/O configuration file is a comma-separated variable (csv) text file that contains all
the information required to configure the AN-X2-MOD-MAS.
Fields can be separated by any whitespace characters such as spaces or tabs, or by
commas.
Anything after a semicolon on a line is treated as a comment. Comments can be inserted
at the end of a line or on a separate line.
Refer to page 26 for a sample configuration file.
I/O Modules
The remote I/O configuration file defines the contents of the drops to be scanned on the
S908 network.
Begin a drop definition with a line that consists of the keyword Drop, followed by an
equals sign and then the drop number, from 1 to 32.
There should be no spaces before or after the equals sign.
Example:
Drop=7
End the drop definition with a line with just the keyword EndDrop.
Between the Drop and EndDrop lines, enter the rack and slot definitions for the drop.
Begin a rack definition with a line that consists of the keyword Rack, followed by an
equals sign and then the rack number, from 1 to 5 for 800 series drops or 1 to 4 for
Quantum drops. There should be no spaces before or after the equals sign.
Example:
Rack=1
After the rack definition, enter the slot definitions. They consist of the keyword Slot,
followed by an equals sign and the slot number, a comma, then the keyword Type, an
equals sign, and the module type. There should be no spaces before or after the equals
sign.
Examples:
Slot=4,Type=B804
Slot=7,Type=ACI_030_00
Summary of Contents for AN-X2-MOD-MAS
Page 1: ...AN X2 MOD MAS Modicon S908 Remote I O Scanner Module User Manual ...
Page 3: ......
Page 49: ...AN X2 MOD MAS Page 49 ...