AN-X accepts RPIs from 1 to 750 ms.
Select an RPI appropriate to the remote I/O network scan time and to your application.
You can use the diagnostic counters (see page 52) to obtain the remote I/O network scan
time.
TIP
The AN-X-MOD-MAS supports Unicast connections from the
ControlLogix.
TIP
Use the web interface of the ENBT module that connects to the AN-X to
view the communication loading of the ENBT module.
Mapping I/O Data
You map Modicon input and output data to the ControlLogix scheduled data by creating a
comma separated variable text file that defines the mappings.
The file consists of sections for each scheduled connection. Within each scheduled
connection there are definitions for the input and output data for that connection that refer
to the Modicon module (drop, rack and slot) where the data is to be found.
When you create a mapping for a module, all the input or output data for the module is
mapped; you cannot map individual registers.
AN-X automatically creates a default mapping file when you autoconfigure I/O. See page
20 for details.