When reading the meter display, all consumption and demand values
must be multiplied by the correct multiplier to calculate actual value.
This includes all register values (kWh, kW, kVARHLg, kVARHLd, etc.) and
phase diagnostic values (real time Amps, Watts, etc.).
Volts, phase angle, frequency and power factor are displayed on the LCD as
actual values and should not be multiplied.
The multiplier value is dependent upon the ratio of the external Current
Transformers (CTs) and can be different for different meter points. Table 7-1
(using 0.1 AMP CTs) and Table 7-2 (using 5.0 AMP CTs) MUST be used to obtain
actual consumption and demand readings.
Table 7-1. Multiplier table for RSM-5c and RSM-5 meter with 0.1 AMP CTs. “XXX” represents
voltage.
Chapter
7
Reading the Display
19
CT Rating
RSM5 XXX CL10
RSM5 XXX CL10 D
RSM5 XXX CL10 M D
RSM5 XXX CL10 RS D
RSM5 XXX CL10 PD
RSM5 480DTACL10 D
RSM5 480DTACL10MD
RSM5 480DTACL10RSD
RSM5 480DTACL10 PD
All RSM5 Kits
Meter Catalog Numbers
50A
100A
200A
400A
600A
800A
1200A
1500A
1600A
2000A
3000A
3200A
4000A
x10.0
x20.0
x40.0
x80.0
x120.0
x160.0
x240.0
x300.0
x320.0
x400.0
x600.0
x640.0
x800.0
Multiplier for 5.0A CT
Table 7-2. Multiplier table for RSM-5 meter with 5.0 AMP CTs. “XXX” represents voltage.
How CT multipliers are calculated
0.1 Amp CTs
The multiplier values for CTs with 0.1A secondary ratings are derived by
dividing the primary side rating by 100. For example, a 50:0.1A-rated CT will
have a multiplier of 50 ÷ 100, which is 0.50. A 100:0.1A rated CT will have a
multiplier of 100 ÷ 100 which is 1.
5.0 Amp CTs
For CTs with 5.0A secondary ratings, the multipliers are derived by dividing
the primary side rating by 5. For example, a 200:5.0A-rated CT will have a
multiplier of 200 ÷ 5, which is 40.
Example:
Meter point with 400:0.1A CT
LCD reading for meter is 3422.119kWh
The correct cumulative consumption (kWh) for this meter is
13688.476
kWh.
(400 ÷ 100 = 4. Multiply face value, for consumption and demand values by 4.
3422.119 x 4 =13688.476)
The multiplier must be applied when calculating both kW and kWH readings on
every screen displayed on the LCD.
Failure to use the appropriate multiplier will result in an incorrect
diagnosis of the meter’s functionality and incorrect revenue billing.
Chapter 7
- Reading the Display -
20
CT Rating
RSM5c XXX
RSM5c XXX D
RSM5c XXX PD
RSM5c 480DTA
RSM5c 480DTA D
RSM5c 480DTA PD
RSM5c XXX 2PH
All RSM5c Kits
RSM5 XXX 01A
RSM5 XXX 01A D
RSM5 XXX 01A M D
RSM5 XXX 01A RS D
RSM5 XXX 01A PD
RSM5 480DTA01A D
RSM5 480DTA01AMD
RSM5 480DTA01ARSD
RSM5 480DTA01A PD
Meter Catalog Numbers
50A
100A
200A
400A
600A
800A
1200A
1500A
1600A
2000A
3000A
3200A
4000A
x0.5
x1.0
x2.0
x4.0
x6.0
x8.0
x12.0
x15.0
x16.0
x20.0
x30.0
x32.0
x40.0
Multiplier for
0.1A CT
RSM-5c
RSM-5
Summary of Contents for RSM-5
Page 1: ...Table of Contents Manual 3 Phase kWh 3 Phase Demand Single Phase kWh ...
Page 2: ...RSM 5c RSM 5 Installation Manual Power Line Communications Metering Systems ...
Page 23: ......
Page 25: ...3 Phase kWh ...
Page 26: ......
Page 27: ......
Page 28: ...3 Phase Demand ...
Page 29: ......
Page 30: ......
Page 31: ...Single Phase kWh ...
Page 32: ......
Page 33: ......