Page 4
7037-141B
March 28, 2012
R
2100 & 4300 Millennium ACC Wood Burner
Draw
ing
not
to
scale
FLOOR PROTECTOR
1.QF.1B
Quadra-fire 2100 & 4300 Millennium ACC do not require a insulating Floor Protector, as they are tested
and comply with the minimum Floor Protector requirements of
AS/NZS 2918:2001
.
Note:
▪
The minimum Floor Protector sizes are specified in the clearance chart, see Table 1 & 2.
▪
A Floor Protector can include ceramic tiles with grouted joints fixed directly onto a wooden floor or a
sheet of toughened glass, panel steel or any other non combustible material laid directly onto a
wooden floor.
▪
If installed directly onto a concrete slab, the concrete slab can be considered as the floor protector,
but must maintain the minimum measurement listed.
PARALLEL POSITIONING
Fig. 3
A
E
B
F
D
C
G
Table 1
DESCRIPTION
Pioneer Double Flue Mounted Shield Universal
Shall be Fitted
With Double Flue
Shield Fitted
2100
4300
A
Min. clearance from firebox to rear wall
150
200
B
Min. clearance from firebox to side wall
550
400
C
Min. distance from firebox opening to floor protector front
300
300
D
Min. distance from firebox to floor protector side
76
69
E
Min. distance from flue centre to side wall
847
730
F
Min distance from rear wall to front of floor protector
1034
1133
G
Width of floor protector
746
798
NOTE: HEAT SHIELD REQUIREMENTS FOR HEAT SENSITIVE WALLS
Clearances may be reduced by provision of an appropriately located heat shield refer to
AS/ NZS 2198:2001 3.2.3 Table 3.1
DESCRIPTION
Pioneer Double Flue Mounted Shield Universal
Shall be Fitted
With Double Flue Shield Fitted
2100-NZ
2100-AU
4300
A
Min. Clearance from firebox to rear wall
150
160
200
B
Min. clearance from firebox to side wall
550
280
400
C
Min. distance from firebox opening to floor protector front
300
300
300
D
Min. distance from firebox to floor protector side
76
76
69
E
Min. distance from flue centre to side wall
847
577
730
F
Min. distance from rear wall to front of floor protector
1034
1043
1133
G
Width of floor protector
746
746
798