background image

March 28, 2012

7037-141B

Page  7

R

2100 & 4300 Millennium ACC Wood Burner

FLUE PENETRATION

 

1.QF.1E

 

C L

 

D

ra

w

in

g n

ot

 to 

sc

al

e

 

12

 

 

 

Tested flue systems, as per AS/NZS 2918:2001

 

 

 

 

 

 

 

Fig. 5

ADD Cowl

 

 

 

Casing Cover

 

 

Spider Bracket

 

oversized casing cover 

is necessary

 

 

minimum 25mm gap 

between flue pipe casing & 

combustible material

 

 

Non combustible material 

Hebel block or 12mm 

Promina board or similar 

under the flashing

 

 

 

 

25 25

 

 

Approved Flashing

 

 

Roof Line

 

 

Inner Casing 200mm 

above roof line

 

 

 

Outer Casing

 

 

Inner Casing

 

 

25 

Internal Swage

 

 

 

 

 

25 25

 

 

 

 

 

12.5

 

 

Vented

 

Ceiling Plate

 

 

 

 

 

 

Pioneer 

Double Flue 

Shield

 

 

Flue Pipe

 

 

 

 

 

 

 

 

 

 

 

CL  

C L

 

 

 

 

 

 

Quadra-fire Millennium

 

 

 

 

 

 

 

Floor

 

Protector

 

FLUE PENETRATION

Summary of Contents for 21M-ACC-NZ

Page 1: ...a ceiling angle greater than 30 refer to Fig 6 7 and AS NZS 2918 2001 4 6 3 b Ceiling Plate may vary in size depending on ceiling angle Please specify ceiling pitch prior to ordering the ceiling plate...

Page 2: ...mm 660mm 247mm 330mm C L 292mm 527mm 406mm C L L C 729mm 668mm 170mm 108mm Outside Air Connection Fig 2 Quadra Fire 4300 Millenium ACC Wood Burner Dimensions roomfor 14x 875 S N 1 5 x 375BarcodeLabel...

Page 3: ...ONFACTORBURNINGSOFTWOOD WHENTESTEDINACCORDANCEWITHAS NZS4013 MAXIMUMAVERAGEHEATOUTPUTBURNINGSOFTWOOD APPROVEDFUEL WETBACK ALLMODELS MANUFACTUREDBY PERFORMANCEMAYVARYFROMTESTVALUESDEPENDINGONACTUAL OPE...

Page 4: ...0 4300 A Min clearance from firebox to rear wall 150 200 B Min clearance from firebox to side wall 550 400 C Min distance from firebox opening to floor protector front 300 300 D Min distance from fire...

Page 5: ...is being used position now Place the firebox on the floor protector to suit the minimum installation clearances See Fig 3 or 4 2 Seismically restrain the firebox and the floor protector to the floor...

Page 6: ...t roof penetration see NZ Building Code E2 Acceptable Solution from 01 07 05 5 Install the outer casing so that i lower end is flush with the underside of the ceiling material and ii with the addition...

Page 7: ...sing cover is necessary minimum 25mm gap between flue pipe casing combustible material Non combustible material Hebel block or 12mm Promina board or similar under the flashing 25 25 Approved Flashing...

Page 8: ...b Fig 4 6 downward distance of casing and 3 x flue distance of the ceiling plate ADD Cowl Casing Cover Spider Bracket Approved Flashing A Ceiling Plate Batten A 3 x flue pipe Ceiling flue pipe Fig 7...

Page 9: ...legs from the bracket 5B leaving the entral tongue to locate inside the flue outlet only Two tabs are provided and if folded back at 90 degrees the bracket and Flue Mounted Shield will mount lower ont...

Page 10: ...MANUFACTURER SHOULD BE CONSULTED IN THE FIRST INSTANCE CAUTIONS CRACKED AND BROKEN COMPONENTS e g GLASS PANELS OR CERAMIC TILES MAY RENDER THE INSTALLATION UNSAFE WARNING ANY MODIFICATION OF THE APPLI...

Page 11: ...March 28 2012 7037 141B Page 11 R 2100 4300 Millennium ACC Wood Burner Homeowner Notes...

Page 12: ...Page 12 7037 141B March 28 2012 R 2100 4300 Millennium ACC Wood Burner Service And Maintenance Log Date of Service Performed By Description of Service...

Page 13: ...ACC STOVE DO NOT DISCARD THIS MANUAL CAUTION Important operating and maintenance instruc tions included Leave this manual with party responsible for use and operation Read understand and follow these...

Reviews: