October 12, 2015
7037-141D
Page 9
2100 & 4300 Millennium ACC Wood Burner
PIONEER DOUBLE FLUE SHIELD FITTING INSTRUCTIONS
1.QF.1G
1. Unpack the Flue Mounted Shield, detach the three brackets and familarize yourself with the
illustrations.
2. Using a sharp knife or razor blade, carefully cut through the plastic film on the “inside face” where
it meets the outer shield (refer sketch). Cut along the full length of the Flue Mounted Shield on
both side, then peel off and fully remove the plastic film from the stainless steel inner shield.
3. Peel back and fully remove the plastic film from the outer shield.
4. Fit the top bracket to the Flue Mounted Shield as illustrated ensuring the rear mid section of the
bracket fits “outside” while the two outer sections of the bracket fit “inside”.
5. Fit the appropriate lower bracket to your woodfire.
Lower Bracket “5B suitable for all other woodfires without an inner rear heatshield.
On certain model woodfires without a raised flue spigot it will be necessary to cut off both the
lower outer legs from the bracket “5B” leaving the entral tongue to locate inside the flue outlet
only.
Two tabs are provided and if folded back at 90 degrees the bracket and Flue Mounted Shield will
mount lower onto the appliance.
The Flue Mounted Shield then locates into the two notches provided n bracket “5B” as illustated.
6. Once the Flue Mounted Shield is fitted in position onto either of the two lower mounting brackets,
check to ensure a large gap is not present between the top of the woodfire and the base of the
Flue Mounted Shield, as this may result in a hot spot on the rear wall directly behind the flue
outlet. If your woodfire has a lift off top grill the Flue Mounted Shield should be raised sufficiently
to enable the top grill to be removed.
7. Using the pre-punched holes in the two tabs provided on the top bracket as guides, drill into the
flue pipe and secure the top bracket to the flue pipe with two stainless steel rivets (not supplied).
MINIMUM HEIGHT OF FLUE SYSTEM EXIT
As per AS/NZS 2918:2001 4.9.1 Fig 4.9
Fig. 8
3000
3000
or less
More than 3000
600 min.
3000
increase from 1000mm
minimum until clear within
3000mm of flue top
increase as necessary
until nothing within
3000mm of flue top
Any nearby structure