December 16, 2011
7037-135H
Page 11
4300 Wood Stove Series (ACC)
R
B. Clearances to Combustibles (UL and ULC)
BACKWALL / SIDEWALL
CORNER INSTALLATION
90° OFF TOP
UP & OUT CEILING
CLEARANCE
STOVE TO CEILING
CLEARANCE
ALCOVE TOP VIEW
A
B
ALCOVE SIDE VIEW
NOTE: Clearances may only be reduced by means
approved by the regulatory authority having jurisdiction
Fire Risk.
• Comply with all minimum clearances to
combustibles as specified.
• Failure to comply may cause house fire.
WARNING
MINIMUM CLEARANCES TO COMBUSTIBLE MATERIALS In Inches & (Millimeters)
NOTE: All "A" , "C" and "F" Dimensions are to the inside diameter of the flue collar.
A
B
C
D
E
F
G
H
INSTALLATION: Full Vertical OR Horizontal with Minimum 2 FT Vertical Off Stove Top
SINGLE WALL PIPE
Flat Top Model
15.5 (394) 11.75 (298) 24.5 (622) 14.5 (368)
10 (254) 17.5 (445) 53.5 (1359) 12 (305)
Step-Top Model
15.5 (394) 11.75 (298) 24.5 (622) 14.5 (368)
2 (51)
12 (305) 49.5 (1283) 12 (305)
DOUBLE WALL PIPE
Flat Top Model
9 (229)
5.25 (133) 24.5 (622) 14.5 (368)
10 (254) 17.5 (445) 53.5 (1359) 12 (305)
Step-Top Model
7.5 (191) 3.75 (95)
22 (559) 11.75 (298)
2 (51)
12 (305) 49.5 (1283) 5 (127)
INSTALLATION: 90° Elbow Off Top of Stove Through Backwall
DOUBLE WALL PIPE
Flat Top Model
8.5 (216)
6 (152)
24.5 (622) 15 (381)
10 (254) 17.5 (445) 53.5(1359)
N/A
Step-Top Model
7.5 (191)
4 (102)
19 (229)
9 (229)
2 (51)
12 (305) 49.5 (1283)
N/A
INSTALLATION: ALCOVE
Six inch (6") (152mm) diameter listed Double Wall air insulated connector pipe with UL103 HT* listed
factory-built Class "A" chimney, or a masonry chimney. (Mobile Home must be equipped with a spark arrestor). Maximum depth of Alcove
shall be no more than 48 inches (1220mm) with a minimum height of 49.5 inches (1283mm) to top of unit, and the referenced clearances.
*In Canada must comply with CAN/ULC-S269 M87 for the 650
o
C Factory-built chimney.
DOUBLE WALL PIPE
Flat Top Model
13 (330)
10 (254)
24 (610) 14.5 (368)
N/A
N/A
53.5 (1359) 12 (305)
Step-Top Model
7.5 (191) 3.75 (95)
22 (584) 11.75 (298)
N/A
N/A
49.5 (1257) 5 (127)
NOTE: Service Space
In order to replace the tube channel assembly a clearance
of 19 inches (483mm) is required on the right side of stove
in order to remove the tubes with the stove in place.
If space is not available, the stove will have to be discon
-
nected from the chimney to proceed with the tube replace
-
ment.
See Figure 36 on page 36.