Page 7
September 1, 2008
5700 ACT Wood Stove
R
250-7090e
FLOOR PROTECTION
16" from glass
8"
USA
Fuel loading door
3-3/16"
4-13/16"
44-9/16"
minimum
33-5/8"
minimum
CANADA
203mm (8")
203mm
(8")
203mm
(8")
457mm (18")
1387mm
(54-9/16")
minimum
1083mm (42-5/8")
minimum
52-13/16 in.
33-5/8 in
.
44-7/8 in
.
29-5/16 in
.
3-1/16 in
.
32-1/16 in.
135°
optional
coverage
must extend 2" beyond each side of pipe
USA
VENT SPECIFICATIONS
Single Wall:
Six inch (6”) (152mm) diameter, minimum 24 MSg black or blued steel connector pipe, with a Listed factory-built
chimney type UL103 HT* suitable for use with solid fuels, or a masonry chimney, and the referenced clearances.
Double Wall:
Six inch (6”) (152mm) diameter, listed double wall air insulated connector pipe with Listed factory-built UL103 HT* Class
“A” chimney, or a masonry chimney (Mobile Home must be equipped with a spark arrestor), and the referenced clearances.
*In Canada must comply with CAN/ULC-S269-for the 650° C Factory-built chimney
FLOOR PROTECTION:
Floor protector must be non-combustible material, extending beneath heater and to the front/sides/rear
as indicated. The floor must be non-combustible or otherwise adequately protected from radiant heat given off by the unit and
from sparks and falling embers. A layer of thin brick or ceramic tile over a combustible floor is not sufficient. A listed hearth pad
that has a “k” value of .84 or lower meets this requirement.
In US installations,
it is necessary to install a floor protector of 1/2" thick metal clad millboard (“k” value = .84) or equivalent at
least 16" (457mm) in front of glass door and 8" (203mm) to both sides of the fuel loading door. Open the door and measure 8”
(203mm) from the side edge of the opening in the face of the stove.
See *exception below.
See Alternate Materials Worksheet on
Page 8
to determine if alternate floor protection materials are acceptable.
I
n Canada,
similar floor protection must be provided 18" (457mm) in front and 8" (203mm) from the sides and rear of the
stove.
See *exception below.
*EXCEPTION:
Non-combustile floor protection must extend beneath the flue pipe when installed with horizontal venting
and extend 2” (51mm) beyond each side.
NOTe: Drawings are for illustration purposes only and are not to scale.
USA - Required
Canada - Recommended
USA