Page 10
7021-130F
May 12, 2014
Castile-B FS Pellet Stove
*L Exception for Horizontal Installations:
See Figure 10 2
USA INSTALLATIONS
: A non-combustible fl oor protection is
recommended extending beneath the fl ue pipe when installed
with horizontal venting or under the Top Vent Adapter with
vertical installation.
CANADA INSTALLATIONS
: A non-combustible fl oor pro-
tection extending beneath the fl ue pipe is
required
with hori-
zontal venting or under the Top Vent Adapter with vertical
installation.
Must extend 2 inches (51mm) beyond each
side of pipe (shaded area)
C. Hearth Pad Requirements (UL and ULC)
Use a non-combustible fl oor protector, extending beneath
appliance and to the front, sides and rear as indicated.
Measure front distance “M” from the surface of the glass
door.
Hearth Pad Requirements
Inches
Millimeters
K
Sides
2
51
L*
Back
2
51
M
Front
6
152
L*
K
K
M
Hearth Pad Requirements
Inches
Millimeters
K
Sides
8
203
L*
Back
2
51
M
Front
18
457
USA Installations
CANADA Installations
Figure 10.2
Figure 10.1