CASTILE FREESTANDING

Mobile Home Installation

You must use a Quadra-Fire Outside Air Kit 

for installation in a mobile home.

1.  An outside air inlet must be provided for the combustion air and 

must remain clear of leaves, debris, ice and/or snow.  It must 

be unrestricted while the appliance is in use to prevent room 

air starvation which causes smoke spillage.  Smoke spillage 

can also set off smoke alarms.  

2.  The combustion air duct system must be made of metal.  It 

must permit zero clearance to combustible construction and 

prevent material from dropping into the inlet or into the area 

beneath the dwelling and contain a rodent screen.

3.  The appliance must be secured to the mobile home structure 

by bolting it to the floor (using lag bolts).  Use the same holes 

that secured the appliance to the shipping pallet.

4.  The appliance must be grounded with #8 solid copper ground

-

ing wire or equivalent, terminated at each end with an NEC 

approved grounding device.

5.  Refer  to  Clearances  to  Combustibles  and  floor  protection 

requirements  on 

page  8

    for  listings  to  combustibles  and 

appropriate chimney systems.

6.  Use silicone to create an effective vapor barrier at the loca

-

tion where the chimney or other component penetrates to the 

exterior of the structure.

7.  Follow the chimney manufacturer’s instructions when installing 

the vent system for use in a mobile home.

8.  Installation shall be in accordance with the Manufacturers Home 

& Safety Standard (HUD) CFR 3280, Part 24.

NEVER INSTALL IN A SLEEPING ROOM.

WARNING

Spark Arestor Cap 

Roof Flashing 

Storm Colla

Joist Shield/Firestop 

Double Wall 

Connector Pipe  

Figure 22.1

CAUTION

Never draw outside combustion air from:

•  Wall, floor or ceiling cavity

•  Enclosed space such as an attic or garage

CAUTION

THE STRUCTURAL INTEGRITY OF THE MOBILE HOME 

FLOOR, WALL AND CEILING/ROOF MUST BE MAINTAINED
Do NOT cut through:

•  Floor joist, wall, studs or ceiling trusses.

•  Any supporting material that would affect the structural 

integrity.

  This appliance is to be connected to a factory-built chimney 

conforming to CAN/ULC-S629, Standard for 650°C Facto

-

ry-Built Chimneys.

  For removal of the chimney for mobile home transportation, 

contact the proper transportation officials.

WARNING

Products of combustion generate carbon monoxide and 

different fuels generate different levels.  Carbon monoxide

• 

Only use approved fuels in this appliance.

• 

Always keep door shut during operation. Operating this 

appliance with doors open can allow CO to leak into the 

home.

CO can kill you before you are aware it is in your home. At 

lower levels of exposure, CO causes mild effects that are often 

mistaken for the flu. These symptoms include headaches, 

dizziness, disorientation, nausea and fatigue. The effects of CO 

exposure can vary greatly from person to person depending 

on age, overall health and the concentration and length of 

exposure.

WARNING

  It is critical to have a working smoke detector installed in 

the home of appliance operation.

 

• 

Smoke alarms that are properly installed and maintained 

play a vital role in reducing fire deaths and injuries. Having 

a working smoke alarm reduces the chance of fire related 

injuries..

Summary of Contents for CASTILE-MBK-B

Page 1: ...minimum clearances to combustibles as specified Failure to comply may cause house fire HOT SURFACES Glass and other surfaces are hot during operation AND cool down Hot glass will cause burns Do not to...

Page 2: ...Components 5 E Install Checklist 6 3 Dimensions and Clearances 7 A Appliance Dimensions 7 B Clearances to Combustibles UL and ULC 8 C Hearth Pad Requirements UL and ULC 8 D Alcove 9 4 Vent Informatio...

Page 3: ...ped with 5mm ceramic glass Replace glass only with 5mm ceramic glass Please con tact your dealer for replacement glass D Electrical Rating 115 VAC 60 Hz Start 4 1 Amps Run 1 1 Amps E Mobile Home Appro...

Page 4: ...the installation Location of the appliance and chimney will affect performance Consideration must be given to Safety convenience traffic flow Placement of the chimney and chimney connector and to mini...

Page 5: ...ermostat Wall Control Location The thermostat wall control s location will have some affect on the appliance s operation Maximum wire length from appliance is 100 feet 30 48m with continuous non splic...

Page 6: ...the party responsible for use and operation ATTENTION INSTALLER Follow this Standard Work Checklist This standard work checklist is to be used by the installer in conjunction with not instead of the...

Page 7: ...7 3 Side View Figure 7 4 Side View with Top Vent Adapter 24 in 609mm 24 5 8 in 626mm 12 in 305mm 24 in 609mm 28 9 16 in 725mm 15 15 16 in 405mm 22 7 8 in 582mm 17 in 431mm 16 5 16 in 414mm 28 3 4 in...

Page 8: ...ecommended extending beneath the flue pipe when installed with horizontal venting or under the Top Vent Adapter with vertical installation CANADA INSTALLATIONS A non combustible floor pro tection exte...

Page 9: ...Illustrations diagrams are not drawn to scale Actual installation may vary due to individual design preference D Alcove Figure 9 1 All minimums listed are to a combustible surface Minimum Maximum Inc...

Page 10: ...protruding parts of the structure P 12 in Clearance above roof line for vertical terminations All minimum clearances are listed with an Outside Air Kit OAK installed unless otherwise noted in table be...

Page 11: ...t with your local HVAC professional to determine the ventilation demands for your house Vent Configurations To reduce probability of reverse drafting during shut down conditions Hearth Home Technologi...

Page 12: ...zontally from c Not less than 12 inches 305mm above 3 Distance from permanently closed windows a Not less than 12 inches 305mm below horizontally from or above 4 Distance between bottom of termination...

Page 13: ...2 If the equivalent length of pipe is 12 feet 3 7m with altitude of 6 000 feet 1829m you may use 3 or 4 inch 76 to 102mm diameter type L or PL vent H Pipe Selection Chart The chart will help you in de...

Page 14: ...cumulate ash and will need to be cleaned more often Try to keep them as short as possible ONE 90 ELBOW Total Horizontal Minimum Vertical Vent Diameter 4 0 3 5 5 3 6 6 3 7 7 3 8 8 4 9 9 4 10 10 4 11 11...

Page 15: ...stalla tions Must use 3 or 4 inch 76 102mm L or PL Listed pellet venting or Listed double wall pipe and a Quadra Fire Outside Air Kit in mobile homes NOTE In Canada where passage through a wall or par...

Page 16: ...an out Cover 24 in 610mm Minimum Ceiling Support 6 in 152mm Flue Connector 6 in 152mm Class A Chimney Connector Adapter 3 in to 6 in 76 152mm Top Vent Kit We recommend a minimum of 60 inches 1524mm ve...

Page 17: ...ce Concrete Cap 1 in 25mm clearance with firestop 6 in 152mm minimum Non combustible Hearth Pad Airtight clean out door Sheathing 2 in 51mm minimum Flashing 1 in 25mm clearance 1 in 25mm clearance wit...

Page 18: ...N Never draw outside combustion air from Wall floor or ceiling cavity Enclosed space such as an attic or garage Flex Hose Hose Clamp Collar Assembly Trim Ring Termination Cap Assembly Hose Clamp Air I...

Page 19: ...hort horizontal pipe in the top vent adapter as a guide Install the 4 screws Figure 19 2 6 Install the vent pipe into the top vent adapter be sure to silicone all joints C Rear Vent Rear Vent to Top V...

Page 20: ...from appliance Do NOT route cord under or in front of appliance CAUTION The appliance comes standard with a wall thermostat and 25 of wire If you need to run more than 25 make sure you use a continuo...

Page 21: ...S FOR THERMOSTAT WIRES POWER OUTLET FUSE Fuse W R Figure 21 2 Press and pull to remove Press and pull to remove Figure 21 3 Thermostat Operation Digital display Digital display Back light Heat On or O...

Page 22: ...3280 Part 24 NEVER INSTALL IN A SLEEPING ROOM WARNING Spark Arestor Cap Roof Flashing Storm Collar Joist Shield Firestop Double Wall Connector Pipe Figure 22 1 CAUTION Never draw outside combustion ai...

Page 23: ...ssembly 7001 044 Outside Air Collar Assembly SRV7001 045 Trim Plate Outside Air Kit 412 7100 Pullrod Handle PULLROD HNDL Smart Batt Il 841 0970 Smart Stat Il 841 0960 Thermostat Mechanical 812 3760 Y...

Page 24: ...purchased installed _________________________________________________________________________ Serial Number ____________________________________ Location on appliance ___________________________ Deale...

Reviews: