Q. Thermostat Temperature Programs

The thermostat by default has 4 separate program events 

they are: MORN, DAY, EVE, and NITE. Each event ends at 

the start time of the following event.

NOTE:

 When the last event is finished for each day or 

group of days, the thermostat will advance forward into 

the next day or group of days.

NOTE:

 If the thermostat is set for 2 events a day instead 

of  4,  the  thermostat  will  only  use  the  DAY  and  NITE 

events.

R. Thermostat Other Features

TEMPERATURE CALIBRATION:

The  internal  temperature  sensor  in  this  thermostat  is 

accurately  calibrated  at  the  factory,  and  in  most  cases 

alterations  to  this  setting  should  not  be  needed.  The 

temperature calibration feature allows you to manually offset 

the measured temperature by as much as plus or minus 5°F 

(3°C) from its original value. If several thermostats are used 

in the same house, this feature can be used to synchronize 

this thermostat to the others.
Change the temperature calibration:
1.  Move TEMPERATURE switch to OFF.
2.  Move SET switch to RUN.
3.  Press and hold both UP and DOWN buttons together for 

at least 5 seconds; the words SET and CAL will appear 

on the display along with a single flashing temperature 

digit.

4.  Use the UP or DOWN buttons to change the number of 

degrees desired for adjustment; 0° is the default value 

and also means no correction will be applied.

5.  Press the NEXT button to accept the setting.

KEYPAD LOCKOUT:

There is the option to lock the front panel buttons to prevent 

unauthorized tampering of your thermostat settings.
To Lock the Keypad:
1.  Move TEMPERATURE switch to HEAT.
2.  Move SET switch to RUN.
3.  Perform  a  single  press  of  each  button  in  the 

following sequence:
•  NEXT, NEXT, NEXT, HOLD

A padlock will appear on the display screen.
To Unlock the Keypad:
1.  Move TEMPERATURE switch to HEAT.
2.  Move SET switch to RUN.
3.  Perform  a  single  press  of  each  button  in  the 

following sequence:
•  NEXT, NEXT, NEXT, HOLD

A padlock will no longer be present on the display screen.

NOTE: 

All other features need to be completed in a timely 

manner as the thermostat will time out after 10 seconds.

NOTE: 

The word COPY will not appear on the display 

for  Monday,  but  will  display  each  day  afterwards  for 

approximately one second and the day of the week will 

automatically advance forward to the next day.

TEMPERATURE HOLD:

Temperature  hold  is  used  for  maintaining  a  fixed  set 

temperature; once a HOLD is initiated, the thermostat will 

maintain the set temperature indefinitely. To enter a HOLD 

state, press the HOLD button one time and the word HOLD 

will appear on the display. To cancel, press the HOLD button 

once again.

6.  Use steps 3 through 5 to set up the events for the rest of 

the week or group of days.

7.  Return the SET switch back to RUN.

COPY PROGRAM FEATURE:

Using similar instructions as set temperature programs the 

COPY button will allow a whole day of set program events 

to be copied to another day.

1.  Move Temperature switch to HEAT as well as move SET 

switch to TEMP PROG position.

2.  Starting with Monday, use the UP or DOWN buttons to 

adjust the start time and set temperature for the MORN, 

DAY,  EVE,  and  NITE  events.  Press  the  COPY  button 

and then press the  NEXT button to advance to Tuesday.

3.  With  Tuesday  displayed  press  COPY  button.  As 

all  programs  events  from  Monday  will  be  copied  to 

Tuesday  (this  will  advance  automatically  to  the  next 

day; Wednesday, as the word COPY will appear on the 

screen for one second).

SET TEMPERATURE PROGRAMS:

1.  Move TEMPERATURE switch to HEAT.

2.  Move SET switch to TEMP PROG position.

3.  Starting with Monday, use the UP or DOWN buttons to 

adjust the start time and set temperature for the MORN 

event, and then press NEXT button to advance.

4.  Adjust  the  start  time  and  set  temperature  of  the  DAY 

event then press NEXT button.

5.  Continue  in  this  same  manner  to  adjust  the  start  time 

and  set  temperatures  for  the  EVE  and  NITE  events 

for Monday

Thermostat  is  protected  against  normal  static  electric 

discharges,  however  to  minimize  the  risk  of  damaging 

the thermostat in extremely dry weather, please touch a 

grounded metal object before touching the thermostat.

STATIC NOTICE

4.  Continue  in  this  pressing  COPY  button  to  set  desired 

days with original setting.

Summary of Contents for CB1200-C

Page 1: ...anual please contact your dealer or visit www quadrafire com REMARQUE Pour obtenir une traduction fran aise de ce manuel s il vous pla t contacter votre revendeur ou visitez www quadrafire com Tested...

Page 2: ...trictions and inspection in your area WARNING FOR MOBILE HOMES Do not install appliance in a sleeping room An outside combustion air inlet must be provided The structural integrity of the mobile home...

Page 3: ...e Safety 8 B Non Combustible Materials 8 C Combustible Materials 8 D Fuel Material and Fuel Storage 8 E Before Your First Fire 9 F Filling the Hopper 9 G General Operating Information 10 H Starting Yo...

Page 4: ...earlier However the Warranty coverage shall commence no later than 24 months following the date of Product shipment from HHT regardless of the installation or occupancy date The term Lifetime in the t...

Page 5: ...forced air furnaces or other such causes 6 use of fuels other than those specified in the operation instructions 7 installation or use of components not supplied with the applicable Product or any ot...

Page 6: ...with the requirements of CSA B415 1 Arange of BTU outputs calculated using HHV efficiency and the burn rates from the EPA tests Based on the maximum feed rate per hour multiplied by approximately 860...

Page 7: ...e properly grounded to the frame of the mobile home and use only Listed pellet vent Class L or PL connector pipe Outside Air Kit part 811 0570 or 811 0872 must be installed in a mobile home installati...

Page 8: ...d maintain regularly Conveniently locate a Class A fire extinguisher to contend with small fires In the event of a hopper fire Evacuate the house immediately Notify fire department B Non Combustible M...

Page 9: ...hat would hinder routine cleaning and maintenance Size Pellets are either 1 4 inch or 5 16 inch 6 8mm in diameter Length should be no more that 1 1 2 inches 38mm Pellet lengths can vary from lot to lo...

Page 10: ...hermostat is calling for heat 6 Once the appliance has ignited let it burn for approximately 15 minutes then set the thermostat to the desired room temperature Adjust the heat output control switch to...

Page 11: ...ld see a fire shortly If not follow Starting Your First Fire on page 10 L Restarting the Appliance Restart Process 1 When the unit has run out of fuel add pellet fuel to the hopper 2 Dump the ashes an...

Page 12: ...RCOAL LIGHTER FLUID OR SIMILAR LIQUIDS TO START OR FRESHEN UP A FIRE IN THIS APPLIANCE DO NOT BURN GARBAGE OR FLAMMABLE FLUIDS SUCH AS GASOLINE NAPHTHA OR ENGINE OIL DO NOT USE CHEMICALS OR FLUIDS TO...

Page 13: ...ries from the desired set point temperature Use the UP DOWN buttons to change the number value between 1 and 9 Generally your system should cycle on about 3 to 6 times per hour A smaller differential...

Page 14: ...eatures need to be completed in a timely manner as the thermostat will time out after 10 seconds NOTE The word COPY will not appear on the display for Monday but will display each day afterwards for a...

Page 15: ...of the thermostat can be removed from the back half by using the tabs on the top edge of the thermostat housing Figure 15 2 HARDWARE RESET The hardware reset button labeled HW RST is a small round pu...

Page 16: ...enance and Service on page 17 What is the metal object with the bend in it that came inside the plastic bag It is a clean out tool used to help clean the fire pot and remove any jams in the rare event...

Page 17: ...l types OR X Top Vent Adapter More frequently depending on the fuel type or ash build up OR X Venting System More frequently depending on the fuel type OR X Follow the detailed instructions found in t...

Page 18: ...move ash with an ash vacuum or whisk broom and small dust pan d This ash is deposited in the same ash pan as the fire pot debris The ash pan should be emptied every time you clean the firebox Remember...

Page 19: ...appliance is allowed to cool has been unplugged and the exhaust blower is off b Empty the hopper of any remaining pellets c Vacuum the hopper and feed tube 6 Cleaning Heat Exchanger Chambers Drop Tub...

Page 20: ...epending on ash build up By Qualified Service Technician Homeowner Be sure the appliance is allowed to cool has been unplugged and the exhaust blower is off The products of combustion will contain sma...

Page 21: ...rom the firebox and vacuum thoroughly c Paint all exposed steel including cast iron Use the Touch Up paint supplied with the appliance or Purchase paint from your local dealer Must use a high temperat...

Page 22: ...Homeowner Poor quality pellet fuel or lack of maintenance can create conditions that make the fire pot fill quickly with ashes and clinkers This condition makes the appliance susceptible to overfilli...

Page 23: ...n fire pot Fire pot clean out plate not closed Fire pot is dirty The ignition hole between the igniter bracket and fire pot is blocked Igniter not working Control box defective Check that fire pot cle...

Page 24: ...t or does not shut off Blower not plugged in Blower is clogged with ash Blower is defective Control box is defective Check that blower is plugged into wire harness Clean exhaust system Replace blower...

Page 25: ...to housing c Re connect wiring use jumper wire if necessary Re connect power supply Remove 2 Screws Remove 4 Screws Outside Air Flex Hose Convection Blower Figure 25 2 5 5 Service Parts Replacement 2...

Page 26: ...and remove the ash drawer 2 Follow instructions to remove the ash pan found on page 18 Cleaning Ash Pan Remove the access plate directly above it by removing the 2 screws just below the ash catcher 3...

Page 27: ...frame and slightly bend up and out of the way d Slide glass out the side and slide new glass in e Re install the side glass frame and tighten the top and bottom frames f Re install the door latch if...

Page 28: ...Check the wall receptacle for 120 volt 60 Hz standard current Make sure the outlet is grounded and has the correct polarity A good surge protector is recommended 13 Red Call Light The red call light i...

Page 29: ...xchanger system is dirty or plugged or if the firebox door is open 21 Wiring Harness See Figure 29 1 below 16 Thermostat The appliance is designed to run on a 12 volt AC thermostat The heat anticipato...

Page 30: ...Tubes Figure 30 2 Power Outlet Terminal Block Center 2 screws for Thermostat Wires Figure 30 3 Figure 30 1 Heat Output Fan Speed Reset Button Call Light HIGH HIGH MED LOW LOW Outside Air Flex Hose Con...

Page 31: ...31 7027 802K 10 21 C Service and Maintenance Log Date of Service Performed By Description of Service...

Page 32: ...32 7027 802K 10 21 Date of Service Performed By Description of Service...

Page 33: ...33 7027 802K 10 21 Date of Service Performed By Description of Service...

Page 34: ...March 2019 Ending Manufacturing Date Active Classic Bay Freestanding Pellet Stove Part number list on following page 04 21 1 6 2 7 8 9 3 4 5 10 11 12 13 14 15 16 17 17 22 18 19 20 21 23 24 25 26 27 3...

Page 35: ...2 Pkg of 12 220 0490 12 Y Hopper Lid Magnetic Switch SRV7000 375 Y 2 Baffle Assembly Left 510 5350 3 Baffle Assembly Right 510 5360 4 Hinge Plate 812 4030 Hinge Door Male SRV450 2810 Screw Pan Head Ph...

Page 36: ...Loop Igniter Pkg of 1 SRV7000 462 Y Pkg of 10 SRV7000 462 10 Y Wing Thumb Screw 8 32 X 1 2 Pkg of 24 7000 223 24 Y 11 2 Combustion Plenum Trap Door 812 4100 12 Thermocouple Cover Qty 1 812 1322 Y Pkg...

Page 37: ...Y 22 Snap Disc Convection Blower 1 SRV230 0060 Y 23 Convection Blower 130 60 CFM 812 3370 Y Nut Keps Lock 8 32 Pkg of 40 226 0060 40 Y Screw Pan Head Philips 8 32 X 3 4 Pkg of 24 229 1100 24 Y 24 Snap...

Page 38: ...Assembly SRV229 0920 36 Control Board 3 Speed SRV7000 704 Y Fuse 8 Amp Control Box Pkg of 10 812 3780 10 Y 37 Cover Control Box 410 6321 38 Feed Adjustment Plate 812 4170 39 Cover Feed Motor SRV7027 0...

Page 39: ...nt 812 3570 Damper 3 Inch Tall Vertical Installs Only PEL DAMP3 Y Damper 4 Inch Tall Vertical Installs Only PEL DAMP4 Heat Exchange Repair Kit 812 4970 Log Set 811 0592 Outside Air Kit Floor 811 0570...

Page 40: ...maintenance instructions included Read understand and follow these instructions for safe installation and operation Leave this manual with party responsible for use and operation of this appliance We...

Reviews: