Page 12
7014-179K
May 6, 2015
R
CB 1200 Pellet Stove
Do not terminate vent
in any enclosed or semi-enclosed
area such as a carport, garage, attic, crawl space, under a
sun deck or porch, narrow walkway or closely fenced area,
or any location that can build up a concentration of fumes
such as a stairwell, covered breezeway, etc.
CAUTION
B. Chimney and Exhaust Connection
1.
Chimney & Connector
: Use 3 or 4 inch (76-102mm)
diameter type "L" or "PL" venting system. It can be vented
vertically or horizontally.
2.
Mobile Home:
Approved for all Listed pellet vent. If using
the 3 inch (76mm) vertical top vent adapter kit or the 3
to 6 inch (76-152mm) top vent offset adapter, use Listed
double wall fl ue connector. A Quadra-Fire outside air kit
must be used with manufactured home installations.
3.
Residential:
The 3 inch (76mm) vertical top vent adapter
kit and the 3 to 6 inch (76-152mm) top vent offset adapter
are tested to use 24 gauge single wall fl ue connector or
Listed double wall fl ue connector to Class A Listed metal
chimneys, or masonry chimneys meeting national and/or
local codes for solid fuel appliances.
4.
INSTALL VENT AT CLEARANCES SPECIFIED BY THE
VENT MANUFACTURER.
5. Secure exhaust venting system to the appliance with at least
3 screws. Also secure all connector pipe joints with at least
3 screws through each joint.
6. DO NOT INSTALL A FLUE DAMPER IN THE EXHAUST
VENTING SYSTEM OF THIS UNIT.
7. DO NOT CONNECT THIS UNIT TO A CHIMNEY FLUE
SERVING ANOTHER APPLIANCE.
NOTE: All pipe must be welded seam pipe whenever pos-
sible. Seal pipe joints with high temperature silicone (500°F
[260°C] minimum rated only). Do not put silicone inside
of pipe.
NOTE: If burning shelled fi eld corn, you must use approved
venting specifi cally designed for corn. Follow the instruc-
tions from the venting manufacturer.
Fire Hazard.
• Only LISTED venting components may be
used.
• NO OTHER vent components may be used.
Substitute or damaged vent components may
impair safe operation.
WARNING
C. Venting Termination Requirements
1
.
Termination must exhaust above air inlet elevation. It is
recommended that at least 60 inches (1524mm) of verti-
cal pipe be installed when appliance is vented directly
through a wall. This will create a natural draft, which
will help prevent the possibility of smoke or odor venting
into the home during a power outage. It will also keep
exhaust from causing a nuisance or hazard by exposing
people or shrubs to high temperatures. The safest and
preferred venting method is to extend the vent vertically
through the roof.
2
.
Distance from
doors and opening windows, or gravity or
ventilation air inlets into building:
a. Not less than 48 inches (1.2m) below;
b. Not less than 48 inches (1.2m) horizontally from;
c. Not less than 12 inches (305mm) above.
3. Distance from permanently closed windows:
a. Not less than 12 inches (305mm) below, horizontally
from or above.
4
.
Distance between
bottom of termination and grade
should be 12 inches (305mm) minimum. This is con-
ditional upon plants in the area, and nature of grade
surface. The grade surface must be a non-combustible
material (i.e., rock, dirt). The grade surface must not be
lawn. Distance between bottom of termination and public
walkway should be 84 inches (2134mm) minimum.
5
.
Distance to combustible
materials must be 24 inches
(610mm) minimum. This includes adjacent buildings,
fences, protruding parts of the structure, roof overhang,
plants and shrubs, etc.
6. Termination Cap Location (Home Electrical Service)
• Side-to-side clearance is to be the same as minimum
clearance to vinyl inside corners.
• Clearance of a termination cap below electrical service
shall be the same as minimum clearance to vinyl soffi ts.
• Clearance of a termination cap above electrical service
will be 12 inches (305mm) minimum.
• Location of the vent termination must not obstruct or
interfere with access to the electrical service.
Vent surfaces get HOT, can cause burns if
touched. Noncombustible shielding or guards
may be required.
WARNING
NOTE
: The appliance exhaust outlet is designed to ac-
commodate 3 inch venting. Use of 4 inch venting requires
the use of a 3-to-4 inch exhaust vent increaser in addition
to any other venting components needed, sold sepa-
rately.
Summary of Contents for CB1200M-MBK
Page 47: ...R May 6 2015 7014 179K Page 47 CB 1200 Pellet Stove E Warranty Policy...
Page 48: ...Page 48 7014 179K May 6 2015 R CB 1200 Pellet Stove...
Page 49: ...R May 6 2015 7014 179K Page 49 CB 1200 Pellet Stove...
Page 50: ...Page 50 7014 179K May 6 2015 R CB 1200 Pellet Stove...
Page 51: ...R May 6 2015 7014 179K Page 51 CB 1200 Pellet Stove...