Quadra-Fire • Columbia Bay • 250-5195 Rev. K
3
Appliance Location and Clearances
A. Selecting Appliance Location
NOTE:
·
Illustrations refl ect typical installations and are FOR
DESIGN PURPOSES ONLY.
·
Illustrations/diagrams are not drawn to scale.
·
Actual installation may vary due to individual design
preference.
When selecting a location for your appliance it is important to
consider the required clearances to walls (see
Figure 3.1
).
WARNING
Fire Risk
Provide adequate clearance:
• Around air openings
• To
combustibles
• For
service
access
Locate appliance away from traffi c areas.
Fire Risk.
•
Locate and install appliance to all
clearance specifi cations in manual.
WARNING
B. Clearances
Figure 3.1
Model
A
A*
B
C
D
E
F
G
H
I
Columbia Bay FS
Inches
6
6-3/4
2
6
14
2
84
19
36
36
Millimeters
152
171
515
152
356
51
2134
483
914
914
NOTE:
Flooring beneath appliance may reach 90 degrees
plus room ambient temperature. Check with flooring
manufacturer for maximum temperature allowed on flooring
surfaces.
It is permissible to place the appliance on carpet.
CAUTION
Some carpet materials may be sensitive to radiant heat from the
appliance causing discoloration or odor.
Fire Risk.
Odor Risk.
Tipping Risk
• Install appliance on a stable, level platform/
fl oor strong enough to support appliance
without tipping.
• USE
wood
fl ooring, ceramic tile, brick hearth
or high pressure laminate fl ooring applied
directly over the sub-fl ooring material.
WARNING
A
B
C
A*
A*
E
D
H
E
F
I
G - Alcove Height
NOTE: For actual appliance dimensions refer to Sec-
tion 12.