Explorer II

D. Chimney Height / Rise and Run

This product was designed for and tested on a 6 inch 

(152mm) chimney, 14 to 16 feet (420-480cm) high, 

(includes appliance height) measured from the base of the 

appliance.  The further your stack height or diameter varies 

from this configuration,  the greater the likelihood it may 

affect performance.

Chimney height may need to be increased by 2 - 3% per 

each 1000 feet above sea level.  It is not recommended to 

use offsets or elbows at altitudes above 4000 feet above 

sea level or when there are other factors that affect flue 

draft.

Fire Risk

.

Inspection of Chimney:

•  Chimney must be in good condition.

•  Meets minimum standard of NFPA 211

•  Factory-built chimney must be 6 inch 

(152mm) UL103 HT.

WARNING

WARNING

Asphyxiation Risk.

• 

DO NOT CONNECT THIS Appliance TO A 

CHIMNEY FLUE SERVICING ANOTHER 

APPLIANCE.

• 

DO NOT CONNECT TO ANY AIR 

DISTRIBUTION DUCT OR SYSTEM.

May allow flue gases to enter the house.

Improper installation, adjustment, alteration, service or 

maintenance can cause injury or property damage. Refer 

to the owner’s information manual provided with this 

appliance. For assistance or additional information consult 

a qualified installer, service agency or your dealer.

WARNING

Floor

Protector

Chimney

Connector

Insulated " T "

Flashing

Listed Termination Cap

Trim Collar on

Inside Wall

Listed Chimney

Storm Collar

Wall Support

Roof Brace (if required)

Thimble

Figure 13.1 Prefabricated Exterior Chimney

E. Venting Components 

Chimney Connector:

It is also known as flue pipe or appliance pipe.  The 

chimney connector joins the appliance to the chimney.  It 

must be a 6 inch (152mm) minimum diameter 24 gauge 

mild steel black or 26 gauge blued steel, or an approved 

air-insulated double wall venting pipe.

  

Thimble

:  

A manufactured or site-constructed device installed in 

combustible walls through which the chimney connector 

passes to the chimney.  It is intended to keep the walls 

from igniting.  Site constructed thimbles must meet NFPA 

211 Standards.  Prefabricated must be suitable for use with 

selected chimney and meet UL103 Type HT Standards.  

Follow instructions provided by the manufacturer for 

manufactured thimbles for masonry chimney and 

prefabricated chimneys.

Chimney

:

The chimney can be new or existing, masonry or 

prefabricated and must meet the following minimum 

requirements and as specified in Section 4F.

NOTE: I

n Canada when using a factory-built chimney it 

must be safety listed,

 Type UL103 HT (2100oF) 

CLASS “A” 

or conforming to 

CAN/ULC-S629M, 

STANDARD FOR 650o

C FACTORY-BUILT 

CHIMNEYS.

F. Chimney Systems

Prefabricated Metal Chimney

• 

Must be minimum 6 inch (152mm) diameter (ID) high 

temperature chimney listed to UL 103 HT (2100

o

F) or 

ULC S629M.

•  Must use components required by the manufacturer for 

installation.

•  Must maintain clearances required by the manufacturer 

for installation.

•  Refer to manufacturers instructions for installation.

Summary of Contents for Explorer II series

Page 1: ...revendeur ou visitez www quadrafire com If the information in these instructions is not followed exactly a fire could result causing property damage personal injury or death WARNING Do not store or us...

Page 2: ...Chimney Termination Requirements 12 C 2 10 3 Rule 12 D Chimney Height Rise and Run 13 E Venting Components 13 F Chimney Systems 13 G Installing Chimney Components 15 H Proper Draft 15 5 Appliance Set...

Page 3: ...from the low and high EPA tests using Douglas Fir dimensional lumber A peak BTU out of the appliance calculated using the maximum first hour burn rate from the High EPA Test and the BTU content of cor...

Page 4: ...affle and other interior components NOTE Hearth Home Technologies manufacturer of this appliance reserves the right to alter its products their specifications and or price without notice Improper inst...

Page 5: ...chimney heights Ideal performance is with height of chimney between 14 16 feet 4 26 4 88m measured from the base of the appliance C Negative Pressure Negative pressure results from the imbalance of ai...

Page 6: ...ling winds during the heating season Ensure adequate outdoor air for all combustion appliances and exhaust equipment Ensure furnace and air conditioning return vents are not located in the immediate v...

Page 7: ...he party responsible for use and operation Hearth Home Technologies recommends the following Photographing the installation and copying this checklist for your file That this checklist remain visible...

Page 8: ...t View Figure 8 3 Side View 12 1 4 514MM 27 686mm 29 737mm 20 508mm 29 737mm Figure 8 2 Top View 13 3 8 340mm 7 8 22mm 2 3 8 60mm 25 7 8 657mm 3 8 9mm 29 737mm Figure 8 4 Side View with horizontal flu...

Page 9: ...he appliance See exception WARNING Fire Risk Hearth pads must be installed exactly as specified High temperatures or hot embers may ignite concealed combustibles Corner hearth pad dimensions with sing...

Page 10: ...4 1175 6 1 2 165 N A N A 55 1397 N A For alcove only Six inch diameter listed Double wall air insulated connector pipe with UL103 HT listed factory built Class A chimney or masonry chimney Maximum dep...

Page 11: ...space enclosed by the building envelope This helps to produce more draft especially during lighting and die down of the fire Penetrate the highest part of the roof This minimizes the affects of wind...

Page 12: ...or when there are other factors that affect flue draft B Chimney Termination Requirements Follow manufacturer s instructions for clearance securing flashing and terminating the chimney Figure 12 1 12...

Page 13: ...Listed Chimney Storm Collar Wall Support Roof Brace if required Thimble Figure 13 1 Prefabricated Exterior Chimney E Venting Components Chimney Connector It is also known as flue pipe or appliance pip...

Page 14: ...ey Figure 14 2 2 Entry hole to masonry chimney must be lined with an 8 inch 203mm minimum diameter clay liner or equivalent secured with refractory mortar 3 Construct a 17 inch x 17 inch 432mm x 432mm...

Page 15: ...is must be at least 24 gauge mild steel or 26 gauge blue steel The sections must be attached to the appliance and to each other with the crimped male end pointing toward the appliance All joints inclu...

Page 16: ...materials from packing box 2 Floor Rear Installation Cut a 4 inch 102mm hole in outside wall or floor to accommodate outside air piping Use 4 inch 102mm aluminum metal flex or rigid piping to directly...

Page 17: ...agnet under the bottom left rear corner See Owner s Manual for detailed operating instructions for the blower and snap disc Figure 17 1 Shock Risk Do NOT remove grounding prong from plug Route cord aw...

Page 18: ...op or rear venting installation The appliance is shipped with the flue collar in the top vent position Converting Collar For Rear Vent Installation and Installing Required Horizontal Flue Shield 1 Rem...

Page 19: ...ion requirements must be followed precisely 9 Use silicone to create an effective vapor barrier at the location where the chimney or other component penetrates to the exterior of the structure NOTE Of...

Page 20: ...20 7061 197P August 13 2018 Explorer II Date of Service Performed By Description of Service 7 Reference Materials A Service Maintenance Log...

Page 21: ...it Floor Rear OAK ACC Outside Air Collar Assembly 7033 039 Outside Air Shield 33271 Y Firescreen SCR 7061 FASTENERS Avk Rivnut Repair Kit 1 4 20 3 8 16 Rivnut Tools RIVNUT REPAIR Y Nut Ser Flange Smal...

Page 22: ...purchased installed _________________________________________________________________________ Serial Number ____________________________________ Location on appliance ___________________________ Deal...

Reviews: