Explorer II Medium Wood Stove

Chimney Height / Rise and Run

This product was designed for and tested on a 6 inch (152mm) 
chimney, 14 to 16 feet (420-480cm) high, (includes stove 
height) measured from the base of the appliance.  The further 
your stack height or diameter varies from this confi guration,  
the greater the likelihood it may affect performance. 

Chimney height may need to be increased by 2  - 3% per 
each 1000 feet above sea level.  It is not recommended to 
use offsets or elbows at altitudes above 4000 feet above sea 
level or when there are other factors that affect fl ue draft.

C. Installing Chimney Components

Chimney Connector

Single wall connector or stove pipe.  

This must be at least 24 gauge mild steel or 26 gauge blue 
steel.  The sections must be attached to the appliance and to 
each other with the crimped (male) end pointing toward the 
stove.  All joints, including the connection at the fl ue collar, 
should be secured with 3 sheet metal screws.  Make sure 
to follow the minimum clearances to combustibles.   Where 
passage through the wall, or partition of combustible con-
struction is desired in Canada, the installation shall conform 
to CAN/CSA-B365.

Factory-built listed chimney connector (vented).

A listed connector (vented) must be used when installing this 
unit in a mobile home.  The listed connectors must conform 
to each other to ensure a proper fi t and seal.

Flue Gas

Direction

Crimped

End

Toward

Stove

Secure pipe sections with a

minimum of 3 screws

Figure 13.2   Chimney Connector  (Stove Pipe)

WARNING

Asphyxiation Risk.

•  DO NOT CONNECT THIS UNIT TO A CHIMNEY 

FLUE SERVICING ANOTHER APPLIANCE.

•  DO NOT CONNECT TO ANY AIR DISTRIBUTION 

DUCT OR SYSTEM.

May allow fl ue gases to enter the house.

Improper installation, adjustment, alteration, service or main-
tenance can cause injury or property damage. Refer to the 
owner’s information manual provided with this appliance. For 
assistance or additional information consult a qualifi ed installer, 
service agency or your dealer.

WARNING

Fire Risk

.

Inspection of Chimney:

•    Chimney must be in good condition.

•    Meets minimum standard of NFPA 211

•  Factory-built chimney must be 6 inch (152mm) UL103 HT.

WARNING

WARNING

ONLY use connector:

•  Within the room, between appliance and ceiling or wall.
Connector shall NOT pass through:
•  Attic or roof space
•  Closet or similar concealed space
•  Floor or ceiling

Maintain minimum clearances to combustibles

Fire Risk.

Follow Chimney Connector Manufacturer’s 
Instructions for Proper Installation.

Chimney Flue

Liner

Fireclay

Liner or

Equivalent

Masonry Chimney

Constructed to NFPA 211

Wall Spacer

Wall Band

Trim Collar

Chimney

 Connector

1 inch (25mm) Air

Space to Chimney

Section

Min. Clearance

2 inch (51mm)

Min. Chimney Clearance to

Wall Spacer and

Combustibles - 2 inch (51mm)

Chimney Section

Figure 13.1

Solid Pack Chimney with Metal Supports as a Thimble 
(Cont’d)

Summary of Contents for EXPLRMED-PBK

Page 1: ...Hearth Home Technologies recommends NFI certified professionals or technicians supervised by an NFI certified professional HOT SURFACES Glass and other surfaces are hot during operation AND cool down...

Page 2: ...y Specifications 3 C Mobile Home Approved USA ONLY 3 D Glass Specifications 3 E Non Combustible Materials 3 F Combustible Materials 3 2 Getting Started 4 A Design and Installation Considerations 4 B F...

Page 3: ...OAK ACC must be installed in a mobile home installation Improper installation adjustment alteration service or maintenance can cause injury or property damage For assistance or additional information...

Page 4: ...practiced evacuation plan consisting of at least two escape routes 4 A plan to deal with a chimney fire as follows In the event of a chimney fire a Evacuate the house immediately b Notify fire depart...

Page 5: ...pped or sealed Attic mounted duct work and air handler joints and seams taped or sealed Basement installations should be avoided WARNING Negative pressure can cause spillage of com bustion fumes soot...

Page 6: ...secured in place with proper clearance Chimney meets recommended height requirements 14 16 feet Roof flashing installed and sealed Terminations installed and sealed Clearances Section 3 Pg 7 Combusti...

Page 7: ...19 1 2 26 3 4 Figure 7 1 Front View Figure 7 2 Side View 12 1 4 20 1 16 7 15 16 27 28 15 16 Figure 7 2 Top View 29 3 25 7 8 22 3 16 Figure 7 4 Side View with horizontal flue 3 Dimensions and Clearance...

Page 8: ...97 FOLLOW PIPE MANUFACTURES CLEARANCES AS REQUIRED Explorer II 10 5 267 20 25 514 13 5 343 55 1397 MINIMUM CLEARANCES TO COMBUSTIBLE MATERIALS in inches Millimeters NOTE All A B and C Dimensions are t...

Page 9: ...ney should Install through the warm space enclosed by the build ing envelope This helps to produce more draft espe cially during lighting and die down of the fire Penetrate the highest part of the roo...

Page 10: ...Minimum 3 ft 91cm Minimum Wall or Parapet Flat Roof E 2 10 3 Rule These are safety requirements and are not meant to assure proper flue draft This appliance is made with a 6 inch 152mm diameter chimne...

Page 11: ...or 26 gauge blued steel or an approved air insulated double wall venting pipe Thimble A manufactured or site constructed device installed in combustible walls through which the chimney connector passe...

Page 12: ...tside dimension frame from 2 x 2 framing lumber to fit into wall opening Inside opening of frame should be no less than 14 inch x 14 inch 356mm x 356mm Figure 12 1 4 Attach the wall spacer to the chim...

Page 13: ...nectors must conform to each other to ensure a proper fit and seal Flue Gas Direction Crimped End Toward Stove Secure pipe sections with a minimum of 3 screws Figure 13 2 Chimney Connector Stove Pipe...

Page 14: ...cessary to install a floor protector of a minimum of 3 8 inch 9 5mm thick metal clad millboard or equivalent a min imum of 16 inches 406mm in front of glass and 8 inches 203mm to both sides of the fue...

Page 15: ...acking box 2 Using a 2 Phillips screw driver attach the flex adapter to the stove using 4 screws Figure 15 1 3 Floor Rear Installation Cut a 4 inch 102mm hole in outside wall or floor to accommodate o...

Page 16: ...lts securing blower onto outer wall of appliance 4 Place the bracket containing the snap disc and magnet under the bottom left rear corner See Owner s Manual for detailed operating instructions for th...

Page 17: ...e collar in the top vent position Converting Collar For Rear Vent Installation and Installing Required Horizontal Flue Shield 1 Remove flue collar 3 Phillips and convection chamber top 2 Phillips 2 Re...

Page 18: ...6 inch 152mm factory built chimney conforming to CAN ULC 629M STANDARD FOR FACTORY BUILT CHIMNEYS 6 Follow the chimney and chimney connector manufacturer s instructions when installing the flue syste...

Page 19: ...BK ACC Blower Control Box W Switch SRV7000 194 Y Component Pack 7033 051 Magnet Round SRV7000 140 Y Snap Disc Bracket Assembly 7033 036 Snap Disc 1 Convection Blower SRV230 0470 Y Speed Control Only R...

Page 20: ...eration DO NOT DISCARD Please contact your Quadra Fire dealer with any questions or concerns For the number of your nearest Quadra Fire dealer log onto www quadrafire com CONTACT INFORMATION This prod...

Reviews: